SEQUENCER CONTROLLER
WITH OR WITHOUT
DIFFERENTIAL PRESSURE MEASUREMENT
Technical Notice
FI 72.0308.0316E
Page 7 sur 15
- 7 -Page 7 sur 15
- 7 - - 7 -
- 7 -
- 7 -
10) Number of outputs setting
Number of output(s) in the cleaning cycle
11) T1 setting:
Pulse time of an output (in 1/100th of second).
12) T2 Setting:
Idle time between two outputs (in seconds).
13) T2A Setting: (if presence of the DP measurement sensor)
Accelerated idle time between two outputs (in seconds).
14) T3 Setting:
Idle time between two cycles (in minutes).
0: inactive.
15) Setting T4:
Maximum non-cleaning time (in hours).
0: inactive.
If the sequencer has not performed any cycle for the set number of hours, the cycle in course ends up (if
stopped on image) and a cleaning cycle is launched.
Comment: the T4 time is initialised at each impulse on an EV.
16) Number of fan stoppage cycles setting:
Define the number of cycles to be carried out at the time of detection of the fan stoppage
0: inactive.
17) Manual running:
The cycle in course terminates and the number of set cycles is carried out without taking into account the
DP order or the input loop control I1.