70
7.6.2
Connecting to a 3G4010CF Interface Device outside Canada
For information on Compatible Receivers see Appendix A - Compatible Receivers on page 78.
A typical connection is shown in Figure 23. The 3G4010CF is powered separately from the
PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive
Communications Interface Board (sold separately) is also required.
Figure 22 Connecting a FACP to a 3G4010CF Interface Device outside Canada
Note:
The DSC interface device 3G4010CF is required if the installation requires UL864
10th edition certification.
Telephone
Line A
Connection
EOL
Line 2
C.O.
Line 1
C.O.
PCS-100
P
OW
E
R
2
4
V
G
N
D
P
G
M4
G
N
D
1
4
V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
AUX SUPPLY
+
-
To GSM/GPRS
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP : X.X.X.X
External IP : X.X.X.X
SG-Systems
Console 2.1
Default Gateway : X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
Router
MR-401
3G4010CF
TRBL
ALARM
RELAY
SPV
RELAY
TRBL
RELAY
NO
C
NO
C
NO
C
MR-401 - 3G4010CF Connection - Typical Diagram
Typical Installation outside Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010CF: 20 feet max.
- Contact DSC to reprogram the zone inputs to match the
FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise
both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF
enclosure above the PS4086
3G4010CF
TRBL
PGM4
COM
Z3
Z2
Z1
T
1
R
1
NC COM NO
DSC
RM-2
Relay
EOL
-
PS4086
Transformer
Battery
DC IN
+12V COM
AC IN
+
ACT LBT
NC COM NO
DSC
RM-2
Relay
EOL
-
+
BAT+ BAT-
3G4010CF
3G4010CF
TRBL
+
-
Addressable module
configured as AC
failure trouble
Addressable module
configured as low
battery trouble
Addressable
module configured
as 3G4010CF radio
trouble