For input circuits the first line shows the programmed message, the second line shows the
status of the circuit and the position of the event in the queue along with the total number of
events in the queue.
Pressing the
INFO
key gives the following additional information.
The first line shows the loop# and the address, the second line shows the date and time when
the event has occurred.
Other events are displayed in the same format with information applicable to that event only.
2. Event logs
The general event log report displays the contents of the general event log on the shared
display which contains the last 400 of any of the following events:
•
Activations of any input circuits.
•
Restoral of non-latching input circuits.
•
Pre-alarm on any device.
•
Initiation of the alarm verification sequence on a verified alarm input.
•
Any system troubles.
•
Activation of any system common control or any command on the command menu.
The report format is similar to the alarm log report. Pressing the
INFO
key shows additional
information about the log.
3. Current levels
The current levels report displays real-time device information for all eligible devices on the
target loop or for all eligible devices on all loops if you specify a target loop or select all.
Eligible devices are those present in the configuration and also those detected as present on
the real loops. You can indicate the device address to start with, but only if you indicated the
loop number as 1, 2, or 3.
Device information consists of the percent of alarm if the device is an input.
1. Enter the loop number of the desired device and press the
Enter
button.
Nverf alm ipt
Active 002/016
Lp:1 Addr:002
Jul 20, 2005 09 :25AM
Loop Number
Loop :__