How to Enable or disable the Positive Alarm Sequence
1. From the Keypad of the FACP press
M
to enter the
Menu
.
2. Using the
Up and Down
cursor buttons, scroll to
Operation
.
3. Press
Enter.
4. In the
Operation Menu
scroll to
Positive Alarm
.
5. Press
Enter
.
6. You will now see the current status of the
Positive Alarm Sequence
and will be
prompted to change status.
Figure 9
Enabling the Positive Alarm Sequence
7. To change the status press
Enter
.
8. To exit without changing the status press
Cancel
.
How to enable the Positive Alarm Sequence in the MGC-400 Configurator
1. In the Job Details window, check the
Positive Alarm Sequence
box.
This option only applies to alarm input devices with the PA flag (F2) set.
5.9
Remote Annunciator Operation
The MR-401 System supports the following types of annunciators (Class B)
•
RAX-LCD-LITE shared display annunciator.
•
RAM-3500-LCD shared display annunciator.
•
Conventional LED/switch annunciators.
Both shared display RAX-LCD-LITE and RAM-3500-LCD annunciators are connected to the
panel via the RS-485 serial link (Class B).
The maximum number of annunciators is seven (7). Configuration of the annunciators is done
via the software configurator.
Note:
Positive Alarm Sequence needs to be configured in the configuration job file
before it is sent to the panel. There will be no notification message advising a
change of status.
Pos Alarm disabled
Enable ? Y
i