42
Once the report is on display it will list all the parameters of all the addresses related to the
device. In this display “Crt.” indicates report line number, “Add” indicates device current
address, “Parm#” indicates the parameter number from the current address, and “Val#”
indicates the parameter value.
5.10.4
Clear Logs
Clears the logs stored in the flash memory.
Press the
Up
and
Down
cursor keys to scroll to the desired log to be cleared and press the
Enter
button.
A message prompts for confirmation.
After confirmation the logs are cleared and the following information message appears:
5.10.5
Walk Test
Initiates a silent or audible Walk Test. The following occurs when in Walk Test mode:
•
Generates a non-latching trouble that clears after exiting the walktest.
•
Cancelling the walk test is done by pressing the
Cancel
button or if no circuit activations
are detected for one hour.
•
Zone indicators, including the Smart Relay Module (SRM-312) function normally during
the test, displaying the input status when it is activated.
•
Other Relays and signal correlations to input circuits are not processed during walk-test.
Correlations to system status will still be processed.
•
All common controls and keys not explicitly required for the walk-test operation are
disabled while the walk-test is active.
•
The alarm verification and waterflow retard operation is disabled on inputs during walk-
test.
During an Audible walk test:
C r t A d d P a r m # V a l
1 0 0 0 0 1 0 0 2
2 0 0 0 0 2 0 3 4
3 0 0 0 0 2 0 0 3
Select Log
1. Alarm Log
2. General Log
3. All Logs
Clear all the
Selected log (s)?Y/N
Log(s) cleared