22
13.
Caution!
The factory default settings do not necessarily have to be changed, although you are free to tailor the UPS to
your specific needs.
Settings
LCD
display
Explanation
Selection
Factory
default
208/220/230/240 V
230V
Output Volt.Setting
O/P V
Setting
Select Nominal Voltage
100/110/115/120/127 V
120V
Input/Frequency
I/P F Setting
Select input frequency
range when UPS goes into
free run mode
±2%
±5%
±7%
±5%
Input/Bypass
Voltage
I/P Bypass
Set
Select Input Voltage range
when bypass is available
±10%
+10/-15%
+15/-20%
+10/-15%
Free Run Mode
Free Run
Set
Select if UPS can run in
Free run mode
(unsynchronized)
ON/OFF
ON
Bypass
Enable/Disable at
Free run mode
Bypass
disable
If Enable is chosen, the
UPS can go to bypass when
unsynchronized.
Disable/Enable
Disable
He mode Setting
HE Mode
Set
Select if UPS runs in high
efficiency mode
ON/OFF
OFF
Force Manual
Bypass
Manual
bypass
Permanently force UPS to
bypass. For service only.**
ON/OFF
OFF
Management of
Load groups
Outlet
Setting
You can put the two load
groups on and off form
front panel
1 ON & 2 ON
1 OFF & 2 ON
1OFF & 2 OFF
1 ON & 2 OFF
Both load
segments
ON
Do Battery Test
Battery Test
Detect battery is normal or
not.
Silence Function
Silence Set
Enable or disable silence
function
ON/OFF
OFF
Number of
External battery
Packs
Bat Cabinet
Set
This setting is needed
For UPS to predict
Backup time
0 (only internal batteries)
1(one external cabinet)
2 (two external cabinets)
0
Site wiring alarm
Sit Fault Set
You can enable or disable
the site wiring alarm
Enable /Disable
Disable
Select Language
Language
Select load language
English, German, French,
Spanish, Italian.
English
Set Generator Mode Generator
Set unit in generator mode.
***
ON/OFF
OFF
Set RS232
communication
RS232
Control
Set RS232 communication
enable or disable
Enable/Disable
Enable
Содержание ROLINE ProSecure II 1000 VA
Страница 1: ...I ROLINE ProSecure II 700 1000 1500 2000 3000VA Standger t 19 Rack 1HE 2HE Bedienungsanleitung...
Страница 13: ...7 Installation der Rack Mount Typen Installation mit unteren Schienen Installation mit hinterem B gel...
Страница 14: ...8 R ckseitenansichten...
Страница 15: ...9...
Страница 30: ...ProSecure II 700 VA 3000 VA UPS User s and Installation Manual...
Страница 43: ...13 Installation of Rack mounted types Installation with bottom bracket Installation with rear bracket...
Страница 44: ...14 Rear panel views PROSECURE II 700 1 5KVA REAR PANEL PROSECURE II 2 3KVA REAR PANEL...