21
Status of the UPS, measurements and alarms are all indicated on the LCD screen.
Figure 6.
Control panel
Normal
display
The UPS status is shown in normal display mode. From here you have a choice to go to UPS meters display and the Setting
display by pushing the button.
UPS meters display
Various measurements are available through the UPS meters display; pressing the button will scroll through the
following meters:
LCD message
Description
O/P VOLT= xxx, xV
Shows Output AC voltage
O/P FREQ= xx, x Hz
Shows Output Frequency
I/P VOL T= xxx, xV
Shows Input AC voltage
I/P FREQ= xx, x Hz
Shows Input Frequency
BAT VOLT= xx,xV
Shows Battery Voltage
O/P LOAD%= xx%
Shows Load % of max load
O/P W= xW
Shows Output Watts
O/P VA= xVA
Shows Output VA
O/P CURR= xA
Shows Output Current
BACKUP TIME= xx min Shows Estimated Backup time in minutes
BAT CHARG= xx%
Shows approximate percentage of Battery capacity
TEMPERATURE= xxC
Shows approximate ambient temperature
BAT PACK NUM= x
Shows External Battery Pack Number
RATING = xxxxVA
Shows UPS Rating
CPU VERSION xx.x
Shows CPU Version
UPS configurations
7.
Various settings that have been chosen are shown in the UPS setting display.
8.
To enter configuration mode, press the button for one second. The first configuration parameter
will be shown on the LCD display.
9.
Press the button to scroll through the parameters.
10.
Press the button to select the parameter.
11.
Press the button to scroll through the options for the selected parameter; Press
the button to select the option.
You may be prompted to save the selection, if so press the button to either confirm or save your
selection. Other options are saved and started automatically. See the table below for further details.
12.
If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the configuration
mode and return to normal mode displaying Line mode.
Содержание ROLINE ProSecure II 1000 VA
Страница 1: ...I ROLINE ProSecure II 700 1000 1500 2000 3000VA Standger t 19 Rack 1HE 2HE Bedienungsanleitung...
Страница 13: ...7 Installation der Rack Mount Typen Installation mit unteren Schienen Installation mit hinterem B gel...
Страница 14: ...8 R ckseitenansichten...
Страница 15: ...9...
Страница 30: ...ProSecure II 700 VA 3000 VA UPS User s and Installation Manual...
Страница 43: ...13 Installation of Rack mounted types Installation with bottom bracket Installation with rear bracket...
Страница 44: ...14 Rear panel views PROSECURE II 700 1 5KVA REAR PANEL PROSECURE II 2 3KVA REAR PANEL...