16 Rev. 1.2 13/01/2021
RESET : ” RT “ RESET TIMES / FUNCTIONS
If you only need to reset the times and functions of default
settings, proceed as follows:
set SEL to display
RT
then press SET to select the
function. At the same time,
DOT 1
will start to flash, press
SET continuously for minimum 5 seconds for
DIGIT 1
and
DIGIT 2
to display
“ – – “
and the operation will be
complete.
RESET : “ RS “ Global Reset
If you need to reset the control unit to the default
configuration, proceed as follows:
set SEL to display
RS
then press SET to select the
function. At the same time,
DOT 1
will start to flash, press
SET continuously for minimum 5 seconds for
DIGIT 1
and
DIGIT 2
to display
“ – – “
and the operation will be
complete.
DIAGNOSTICS :
Photocell Test:
The control unit is designed for the connection of safety
devices that comply with point 5.1.1.6 of standard EN
12453. W ith every operation cycle, it performs a test of
the operating photocell connected. If there is no
connection and/or non operation, the control unit does not
enable gate motion, and will visually report the failed test
by Display with the
TP
message. Once the photocell is
running correctly again, the control unit is ready for
normal operation. This ensures monitoring against
failures, in compliance with EN 954-1, Category 2.
Control input test:
On each low voltage control input, the control unit uses a LED
signal to make the status readily known.