TECHNICAL
BULLETIN
Product:
Document #:
Rev:
Page:
ALL GYROS
90236
1
3 of 4
ELECTRICAL CONNECTIONS TO ALTERNATE POWER SOURCES
Figure 4: Installation for a Single-Phase 115 VAC Generator System w/o available Neutral
If the generator output is 380 VAC, a transformer will be required to step the voltage down from
380 VAC to 230 VAC. The transformer should have the following ratings:
Primary:
380 VAC
VA Rating:
3 kVA
Secondary:
230 VAC
Type: Marine Grade, Auto or Isolation transformer
The transformer should be configured as shown in Figure 5. Insure that a qualified electrician does the
wiring and follows the installation and wiring instructions provided by the generator and transformer
manufacturer.
Figure 5: Installation for a 3-Phase 380 VAC Generator System
If the generator output is 480 VAC, a transformer will be required to step the voltage down from
480 VAC to 230 VAC. The transformer should have the following ratings:
Primary:
480 VAC
VA Rating:
3 kVA
Secondary:
230 VAC
Type: Marine Grade, Auto or Isolation transformer
The transformer should be configured as shown in Figure 6. Insure that a qualified electrician does the
wiring and follows the installation and wiring instructions provided by the generator and transformer
manufacturer.
Figure 6: Installation for a 3-Pahse 480 VAC Generator System
Содержание 5500 GYRO
Страница 1: ...Rev 2 JULY 2013 INSTALLATION MANUAL MODEL 5500 GYRO...
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 48: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 58: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 62: ...THIS PAGE INTENTIONALLY LEFT BLANK...