GSM-R4-DIN_EN (Version 1.02; 2016-04-06)
Page #3 of 5
Command
This part of a message specifies a requested action. See the following table for
available commands.
GSM
rele
4
commands are not a case sensitive, it’s possible to
use upper letters as well as lower letters.
Command
Parameter
Meaning
Y3 ON
-
An OUTPUT 3 will be switched on.
(Use Y4 ON for OUTPUT 4)
ON
-
This command acts in exactly the same way as
command ON3
Y3 OFF
3 or 4
An OUTPUT 3 will be switched off.
(Use V4 OFF for OUTPUT 4)
OFF
This command acts in exactly the same way as
command OFF3
Y3 PULSE
Y3 RESET
4
Generates 4 sec pulse on OUTPUT 3
Generates 4 sec reset on OUTPUT 3
PULSE
RESET
These commands act in exactly the same way as
command PULSE3 / RESET3.
REG
0 to 55
Setting of requested temperature and starts
regulation mode.
STATE
-
Request of status SMS (state of inputs, outputs,
temperatures, signal quality and credit).
Tip:
It’s possible to use more commands in one SMS. Commands are separated by a
space (see an example).
Examples:
1234 ON
… an appliance connected to OUTPUT3 will be switched on
1234 Y3 ON
… an appliance connected to OUTPUT3 will be switched on
1234 Y4 ON
… an appliance connected to OUTPUT4 will be switched off
1234 Y4 PULSE 5
… an OUTPUT 4 will be switched on and then after 5 seconds
will be switched off (Notes: if an output is already switched on, it will be just switched
off after 5 seconds)
1234 Y4 REG 5
… requested temperature for the function temperature
regulation of OUTPUT 4 will be set to + 5°C
an example of more commands in one SMS:
1234 Y3 OFF Y4 REG 25
… An OUTPUT 3 will be switched off and the requested
temperature will be set to 25°C
Confirmation
If a command message contains a valid password (access code) the
GSM
rele
4
returns
a confirmation message which informs if a command was accepted (see chapter Status
SMS). If you don’t want a confirmation message (e. g. when sending a command SMS
from the Internet GSM gates) add a command “NOBACK”.
Command
Meaning
NOBACK
No confirmation SMS will be sent
Example:
1234 Y3 ON NOBACK
… an appliance connected to OUTPUT3 will be
switched on. NO status message will be sent back
7.3
Local control using pushbuttons
GSM
rele
4
has 2 pushbuttons for local control of outputs (see. Chapter 5.2)
7.4
Status SMS message
Whenever the command SMS contains valid password the
GSM
rele
4
send back Status
message.
Parameter Credit is sent only in case of pre-paid SIM cards. If the actual value of
Credit cannot be readout from operator, the last known value is listed in parentheses
e.g. Credit=(243.15 Kc).
Example of status SMS
Explanation
Base station: Y3 REG 25/27'C OK;
Device name:
Command confirmation: Y3 REG27
X1=ON
INPUT 1 state
X2=ON
INPUT 2 state
Y3=ON(REG 25/27'C)
OUTPUT 3 state
Y4=OFF
OUTPUT 4 state
T5=25'C
INPUT T5 actual temperature
T6=26'C
INPUT T6 actual temperature
Power=Failure
Power supply from 230V
AC
/ (from battery)
Signal=38%
GSM signal level
Credit=243.15 Kc
Credit on pre-paid SIM card
7.5
Remote Control via the application for OS
Android
The application for OS Android called
SeaControl
is used for control and monitoring
of GSM RELAY, you can download it for free. For detailed information and downloading
the application, go to www.seapraha.cz and write GSM-CONTROL into the searchbox.
This application communicates with a GSM relay via SMS.
8.
Warranty
General warranty period is 12 months after purchase, when eventual malfunction
device will be repaired free of charge in SEA company while shipping to SEA is paid by
customer and SEA pays for shipping back to customer. For SW there is 24 months
warranty under following conditions:
Both CPU and PC software is sold “as is”. The software was created by the best
software engineers in SEA and was carefully tested both in SEA and also by SEA
customers using GSM applications products made in SEA. In spite of making all
possible to get error free software it can happen, that the software in CPU or PC
programming SW or their mutual interaction has some error under some specific
conditions. If such error is found and the description of the problem
including configuration file is sent by E-mail to SEA ltd., the error is
removed free of charge and SEA will send new SW by E-mail to
customer.
SEA ltd. has NO RESPONSIBILITY for any damage, lost, costs and
any other problems direct or inducted, caused by such SW error, by
eventual device malfunction from any reason or by undelivered SMS
from the device.
CE Declaration of conformity
in accordance with the Radio and Telecommunications Terminal Equipment Directive 1999/5/EC (R&TTE) and Directive
2011/65/EU (ROHS).
We
SEA, spol. s r.o., Dolnoměcholupská 1537/21, CZ 102 00 Praha 10, Czech Republic,
ID
: 47117931 (
manufacturer
)
declare under our sole responsibility, that product
device for remote control and monitoring
type
GSM-R4-DIN
is in conformity with the following standards:
health and safety:
EN 60 950-1:2005+A1:2009 EN 60 950-1:2006+A11:2009+A1:2010+A12:2011
EMC:
ETSI EN 301 489-1
ETSI EN 301 489-7 v1.3.1
radio frequency:
EN 301 511 v 9.0.2
The last two digits of year in which the CE marking was affixed:
14
Place of issue:
Praha
Name:
Ing. Mario Vejlupek
Date of issue:
18.12.2014
Grade: