2. SpecificationS
this appliance and flue were tested at the following clearances.
the axis i1000 Single sided free standing appliance and flo-met universal 8” flue system with a painted
solid casing between the appliance and ceiling conforming to joint australian/new Zealand Standards
2918:2001, appendix B.
a minimum 1055mm deep X 1220mm wide and 9mm non-combustible hearth should be used under the
appliance and in front of the appliance door when installing the appliance (see joint aS/nZs 2918:2001
3.3.2). the floor protector should extend 550mm in front of the appliance fuel loading door and be
placed centrally in the 1220mm width.
***the appliance must be elevated a minimum of 250mm above the hearth(on a non combustible
surface). if the heater is placed directly onto the hearth, the hearth dimensions required will be greater.
please refer to aS/nZS 2918:2001 as per the minimum for a non-tested appliance.
clearances & Hearth- axis i1000 Single Sided
Co
M
bust
ibl
E W
alls
CoMbustiblE Walls
450MM
250MM
sWing Door
aPPlianCE
550
MM
hEarth
1055
MM
1220MM
Co
Mbust
ibl
E W
alls
Co
Mbust
ibl
E W
alls
aPPlianCE
150MM
150MM
hEarth
sWing Door
1055
MM
1220MM
550
MM
Position a ParallEl Position
diagram not to scale
Position b CornEr Position
diagram not to scale