Operational Characteristics
Water Solenoid Valve
.25 GPM flow rate
Evaporator
Stainless steel
Refrigerant Charge
6.75 oz. of R-134a
Running amps
3.5
Cutter grid
8.5 volts
1.9 amps
Evaporator thermostat
Cut in: 38
o
F.
Cut out: 10 to -4
o
F.
Bin thermostat
Cut in: 41
o
F.
Cut out: 35
o
F.
System Pressures
Temperature
Suction Pressure at the
end of the freeze cycle
(PSIG)
Discharge pressure at
the end of the freeze
cycle (PSIG)
Cycle time in minutes
Air 70
o
F., water 60
o
F.
1 - 4
65 - 80
18 - 22
Air 90
o
F., water 60
o
F.
2 - 5
85 - 100
21 - 27
Air 100
o
F., water 60
o
F.
2 - 8
85 - 105
28 - 35
Air 70
o
F., water 80
o
F.
1 - 4
65 - 80
20 - 25
Air 90
o
F., water 80
o
F.
2 - 5
85 - 100
23 - 30
Air 100
o
F., water 80
o
F.
2 - 6
85 - 105
30 - 38
CSWE1
December 1995
Page 14