SYMPTON
POSSIBLE CAUSE
SUGGESTED CORRECTION
Shortage of water
Water spilling out through curtain
Check or replace curtain
Water solenoid valve not opening
Replace valve
Water leak in sump area
Locate and repair
Water flow control plugged
Replace water inlet valve
Leak of water drain valve
Replace valve
Irregular cubes size & some
Some jets plugged
Remove jet cover and clean
cloudy
Shortage of water
See shortage of water
Unit not level
Level as required
Cubes too large
Freezing cycle too long
Review setting of DIP SWITCH keys
Decreased ice capacity
Inefficient compressor
Replace
Leaky water valve
Repair or replace
Non-condensable gas in system
Purge the system
Poor air circulation or excessive
Relocate the unit or provide for
hot location (Red-alarm LED glows)
more ventilation
Overcharge of refrigerant
Correct the charge. Purge off slowly
Capillary tube partially restricted
Blow charge, add new gas & drier,
after evacuating system with
vacuum pump
Hot gas solenoid valve leaking
Replace valve
Short of refrigerant
Charge to data plate indication
Discharge head pressure too high
See incorrect discharge pressure
Poor harvest
Restriction in incoming water line
Check water valve strainer and flow
control. If necessary enlarge the
flow control orifice
Water inlet valve not opening
Valve coil with open winding
Replace valve
Hot gas valve orifice restricted
Replace hot gas valve assy
Clogged air vented holes in mold cups
Clean out holes plugged
Discharge head pressure too low
See incorrect discharge pressure