SCOPE COMMUNICATIONS UK LTD
PAGETEK PRO MK2
Ref: PTPROMK2INSTALLred
Page
21
of 27
Issue 1
vii) BATTERY FAULT
a) If the battery loses connection or develops a fault, this will be indicated within 25
minutes of its occurrence on the status display as “BATTERY FAULT”. The yellow fault
LED will light and the sounder will beep every second.
b) An “Other Fault” message will be transmitted, which may be received by a suitably
programmed pager or group of pagers if required (must be specified at time of ordering).
c) The Common Fault output to the host Fire Alarm panel (normally open relay contact) will
change to the closed state.
viii) LOW BAT CHARGING
a) After indication of the “LOW BATTERY” condition, when mains is restored the display
will change to “LOW BAT CHARGING” and the yellow fault LED will flash. Note that the
Common Fault relay output will remain closed until the battery has charged above the
minimum threshold (11.5V). After this point, the display will revert to “SYSTEM HEALTH
OK”, the Common Fault relay will unlatch and the Fault LED will extinguish.
Note: for all the above listed fault conditions, the Common Fault output will remain
in the closed state until the last remaining fault has cleared.
Fault Status Display Summary