of 27
Issue 1
6) Fire Alarm Condition
a) If any of the three Fire inputs are activated (by going open circuit), the system will enter
the prioritised Fire alert condition and will transmit the Fire message to all pagers. The
transmission will be repeated every 10 seconds until the system is reset (see Section 7).
b) The status display will indicate the zone activated e.g. “FIRE ZONE 1”, the red transmit
LED will light and the sounder will alert continuously. This condition will remain “locked”
until the system is manually reset. See diagram 8.
c) Where more than one zone is activated, the display will read:
“FIRE ZONE 1+2”
(Inputs 1 & 2 activated)
“FIRE ZONE 1+2+3”
(Inputs 1 & 2 & 3 activated)
“FIRE ZONE 1+3”
(Inputs 1 & 3 activated)
“FIRE ZONE 2+3”
(Inputs 2 & 3 activated)
d) The Fire messages will always be prioritised and displayed/transmitted ahead of any
other messages.
Note: if any Fire input changes state back from open (triggered) to closed, the Fire
alert condition will still remain until the Pagetek Pro MK2 system is either manually
or auto reset.
7) System Reset
a) After a Fire Alert condition, the system must be *manually reset to cancel the alarm.
This task must only be performed by an authorised person who has received adequate
training in the safe operation of the system.
*[unless the system is auto-reset by the Fire panel using the Reset input]
b) Using the front panel keyswitch, insert the key and turn it anti-clockwise to initiate a
Reset and cancel the Fire Alert condition. This will silence the sounder, extinguish the red
LED and the display will revert to “SYSTEM HEALTH OK”