5
Date Code 20170804
Quick-Start Guide
SEL-300G Relay
Relay Commissioning Procedure
Commissioning Procedure
Figure 3
SEL-300G to Computer—C227A and C234A
Step 9. SEL relays respond to ASCII text commands entered on the
relay serial port. PC terminal emulation packages and many
other packages allow ASCII commands to be sent from the PC
serial port and relay responses displayed. Start your PC and run
the appropriate terminal emulation software.
Step 10. Configure the terminal emulation software to operate the PC-
COM port (COM1, COM2, etc.) at the relay baud rate (factory
default 2400 baud), using 8 data bits, 1 stop bit, no parity bit,
All EIA-232 ports (with SEL-2800
transceiver)
SEL-2600 Series RTD Module
C805Z010VVX0003 (3 meters)
d
All EIA-232 ports (with
SEL-2812MR transceiver)
SEL-2664 Field Ground Module
SEL C805 Multimode 200 µm core
diameter fiber-optic cable with ST
connectors, or SEL C807 Multimode
62.5 µm core diameter fiber-optic
cable with ST connectors
a
Data Terminal Equipment.
b
A corresponding main board jumper must be installed to power the dial-up modem with +5 Vdc (0.5 A limit) from the SEL-300G. See
Figure 20 and Table 11.
c
Data Communication Equipment.
d
Refer to the Model Option Table for additional cable choices.
Table 1
Communication Cables to Connect the SEL-300G Relay to Other Devices
(Sheet 2 of 2)
SEL-300G EIA-232 Serial
Ports
Connect to Device (Gender Refers to the Device)
SEL Cable #
HINT:
For the best display, use
VT-100 terminal emulation or the
closest variation.
NOTE:
Commands you type appear
in bold/uppercase:
OTTER
.
Computer keys you press appear in
bold/uppercase/brackets: <
ENTER
>.
Содержание SEL-300G
Страница 1: ...20170804 SEL 300G Multifunction Generator Relay Quick Start Guide PM300GQS 01 ...
Страница 4: ...This page intentionally left blank ...
Страница 6: ...This page intentionally left blank ...
Страница 8: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 55: ......
Страница 56: ......