2
SEL-300G Relay
Quick-Start Guide
Date Code 20170804
Relay Commissioning Procedure
Commissioning Procedure
Commissioning
Procedure
Figure 1
Relay Commissioning Flowchart (refer to text for detailed instructions)
STEP 8
Connect PC
to Relay
STEP 7
Energize
Relay
STEP 5
Contact Output
DC Polarity
Checks
STEP 4
Power Supply
DC Polarity
Checks
(See Fig 7.6)
STEP 3
Modify Circuit
Board Jumpers
STEP 2
AC & DC
Continuity
Checks
STEP 1
Remove DC
Power
STEP 6
Remove AC
Signals
STEP 16
Confirm
Tripping
Settings
STEP 15
Perform
Protection
Element Tests
STEP 13
Verify Contact
Input Operation
STEP 12
Verify AC
Wiring
(See Fig 3 & 4)
STEP 11
Enter Relay
Settings
STEP 10
Configure
Emulation
Software
STEP 9
Run Emulation
Software
STEP 14
Verify Contact
Output
Operation
STEP 18
Operate
Generator at
No Load
STEP 17
Connect Relay
for Tripping
Duty
STEP 19
Operate
Generator at
10% Load
Record
No Load
Third-Harmonic
Voltages
STEP 23
Clear Relay
Data Buffers
STEP 22
Calculate and
Enter 64G
Element Settings
STEP 21
Shut Down
Generator
Correct
Current
Connections
Shut Down
Generator
STEP 20
Operate Generator
at Full Load.
Record Third
Harmonic
Voltages.
Correct
Voltage
Connections
Are Current
Signals Correct?
Are Voltage
Signals Correct?
Are 64G Element
Settings Final?
Start
End
Yes
Yes
Yes
No
No
No
Содержание SEL-300G
Страница 1: ...20170804 SEL 300G Multifunction Generator Relay Quick Start Guide PM300GQS 01 ...
Страница 4: ...This page intentionally left blank ...
Страница 6: ...This page intentionally left blank ...
Страница 8: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 55: ......
Страница 56: ......