701 Motor Protection Relay
ASCII Serial Port Operation
Command Explanations
6.17
=>
METER E
SEL-701 Date: 08/01/1999 Time: 15:59:41.738
MOTOR RELAY
MWhr MVARhr-IN MVARhr-OUT MVAhr
3.4 1.7 0.0 4.5
LAST RESET 07/02/1999 11:10:05.370
=>
Figure 6.10
METER E Command Example.
Maximum/Minimum Metering: METER M
The
METER M
command displays the maximum and minimum values of
assorted current, voltage, power, and temperature quantities. The relay begins updating
the maximum and minimum quantities 30 cycles after the motor starts. Voltage values
are only updated if the phase-to-phase voltage is greater than 13 V secondary. Residual
voltage, if wye-potentials are connected, is only updated if the voltage is greater than
3 V secondary.
=>
METER M
SEL-701 Date: 08/21/1999 Time: 15:59:53.365
MOTOR RELAY
Max Date Time Min Date Time
IA(A) 400.0 07/20/1999 14:00:36.676 15.6 07/02/1999 18:20:00.615
IB(A) 399.3 07/20/1999 14:00:36.726 19.6 07/02/1999 17:48:24.444
IC(A) 398.7 07/20/1999 14:00:36.676 19.1 07/02/1999 17:50:12.939
IN(A) 0.1 07/02/1999 17:53:21.805 0.1 07/02/1999 17:53:21.805
IG(A) 23.5 08/01/1999 15:44:54.574 1.5 07/02/1999 17:42:12.187
VAB(V) 470 07/02/1999 18:29:45.812 72 07/02/1999 18:28:49.100
VBC(V) 465 08/01/1999 15:33:17.710 200 07/20/1999 13:45:42.984
VCA(V) 464 07/20/1999 13:28:21.973 86 07/20/1999 13:45:43.971
VG(V) RESET RESET
kW3P 159.7 07/20/1999 14:00:36.755 0.0 07/02/1999 18:26:44.964
kVAR3P 15.7 07/02/1999 18:29:34.063 -0.0 07/02/1999 18:29:48.921
kVA3P 159.6 07/20/1999 14:35:26.772 2.3 07/02/1999 18:28:48.928
1 WDG (F) 161 07/20/1999 14:32:18.416 118 07/14/1999 04:44:36.676
2 WDG (F) 158 07/20/1999 14:33:26.356 124 07/14/1999 04:36:58.786
3 WDG (F) 155 07/20/1999 14:38:14.284 116 07/14/1999 04:42:32.476
4 WDG (F) 164 07/20/1999 14:31:34.676 128 07/14/1999 04:40:14.135
5 WDG (F) 150 07/20/1999 14:40:46.763 115 07/14/1999 04:39:28.616
6 WDG (F) 158 07/20/1999 14:36:33.656 121 07/14/1999 04:39:40.526
7 BRG (F) 120 07/20/1999 14:20:36.476 74 07/14/1999 04:45:34.873
8 BRG (F) 112 07/20/1999 14:18:58.067 78 07/14/1999 04:44:56.908
9 BRG (F) 114 07/20/1999 14:35:32.985 76 07/14/1999 04:35:46.089
10 BRG (F) 109 07/20/1999 14:30:16.975 81 07/14/1999 04:36:18.542
11 AMB (F) 98 07/20/1999 14:28:38.186 62 07/14/1999 04:38:36.458
LAST RESET 07/02/1999 11:09:10.745
=>
Figure 6.11
METER M Command Example.
Thermal & RTD Metering: METER T
The
METER T
command displays the temperatures of any connected RTDs. This
command also shows the motor current in % of Full Load Amps, the present thermal
model % Thermal Capacity, and the RTD % Thermal Capacity if ambient and winding
temperatures are monitored and a winding RTD trip temperature is set. If the motor is
Содержание SEL-701
Страница 12: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 36: ...This page intentionally left blank ...
Страница 64: ...This page intentionally left blank ...
Страница 144: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 232: ...This page intentionally left blank ...
Страница 246: ...This page intentionally left blank ...
Страница 346: ...This page intentionally left blank ...
Страница 390: ...This page intentionally left blank ...
Страница 408: ...This page intentionally left blank ...
Страница 410: ......
Страница 412: ......
Страница 414: ......
Страница 416: ......
Страница 418: ......
Страница 420: ......
Страница 422: ......
Страница 424: ......
Страница 426: ......
Страница 428: ......
Страница 430: ......
Страница 432: ......
Страница 434: ......
Страница 436: ......
Страница 438: ......
Страница 440: ......
Страница 442: ......
Страница 452: ...This page intentionally left blank ...
Страница 466: ...This page intentionally left blank ...