Date Code 20011009
SEL-701-1 Monitor
SEL-2020/SEL-2030 Compatibility Features
CASCII Command
D.21
"CME E",1,"yyyy"<CR>
"1H","FID","yyyy"<CR>
"1D","45S","yyyy"<CR>
"7H","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC,"yyyy"<CR>
"1D","I","I","I","I","I","I","I","yyyy",<CR>
"4H","MWhr","MVARhr-IN",”MVARhr-OUT”,"MVAhr","yyyy"<CR>
"1D","F","F","F","F","yyyy"<CR>
"1H","LAST RESET","yyyy"<CR>
"1D","23S","yyyy"<CR>
"CME M",1,"yyyy"<CR>
"1H","FID","yyyy"<CR>
"1D","45S","yyyy"<CR>
"7H","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC,"yyyy"<CR>
"1D","I","I","I","I","I","I","I","yyyy"<CR>
"7H","CHANNEL","MAX","DATE","TIME","MIN","DATE","TIME","yyyy"<CR>
"24D","12S","10S","10S","12S","10S","10S","12S","yyyy"<CR>
"1H","LAST RESET","yyyy"<CR>
"1D","23S","yyyy"<CR>
"CME T",1,"yyyy"<CR>
"1H","FID","yyyy"<CR>
"1D","45S","yyyy"<CR>
"7H","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC,"yyyy"<CR>
"1D","I","I","I","I","I","I","I","yyyy"<CR>
"18H","1 BRG (C)","2 BRG (C)","3 BRG (C)","4 BRG (C)","5 BRG (C)","6 BRG (C)","7 WDG (C)","8 WDG
(C)","9 WDG (C)","10 WDG (C)","11 AMB (C)","12 OTH
(C)","FLA(%)","THM CAP(%)","RTD TC(%)","CALC TIME","MINUTES","STARTS","yyyy"<CR>
"1D","10S","10S","10S","10S","10S","10S","10S","10S","10S","10S","10S","10S","F","F","F","I","I","
I","yyyy"<CR>
<ETX>
See the
for definition of the “Names of elements in
the Relay Word separated by spaces” field.
In all instances, if the monitor does not support voltage measurement, the voltage
and power labels are replaced with “*”. The CME E report is not included if voltage
inputs are not supported.
If the monitor is not equipped with internal or external RTD inputs, the RTD
labels are replaced with “*”. If the monitor is equipped with RTD inputs, the RTD
locations (BRG, WDG, etc.) are setting dependent. If Fahrenheit is the designated
temperature scale, the temperature designator (C) is replaced with (F)
where:
"THM CAP(%)" is the thermal model thermal capacity used in
percent.
"RTD TC(%)" is the RTD estimated thermal capacity used in
percent.
"CALC TIME" is the calculated time to thermal trip in seconds.
"MINUTES" is the number of minutes since the last motor start.
"STARTS" is the number of motor starts in the past hour.
Содержание SEL-701-1
Страница 16: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 34: ...This page intentionally left blank ...
Страница 118: ...This page intentionally left blank ...
Страница 142: ...This page intentionally left blank ...
Страница 196: ...This page intentionally left blank ...
Страница 210: ...This page intentionally left blank ...
Страница 242: ...This page intentionally left blank ...
Страница 384: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 452: ...This page intentionally left blank ...