Date Code 20011009
SEL-701-1 Monitor
ASCII Serial Port Operation
Command Explanations
5.17
=>
METER E
SEL-701-1
Date: 08/15/2001 Time: 19:59:41.738
MONITOR
MWhr MVARhr-IN MVARhr-OUT MVAhr
3.4 1.7 0.0 4.5
LAST RESET 08/15/2001 11:10:05.370
=>
Figure 5.10
METER E Command Example.
Maximum/Minimum Metering: METER M
The
METER M
command displays the maximum and minimum values of
assorted current, voltage, power, and temperature quantities. The monitor begins
updating the maximum and minimum quantities 30 cycles after the motor starts.
Voltage values are only updated if the phase-to-phase voltage is greater than 13 V
secondary. Residual voltage, if wye-potentials are connected, is only updated if the
voltage is greater than 3 V secondary.
=>
METER M
SEL-701-1
Date: 08/15/2001 Time: 19:59:53.365
MONITOR
Max Date Time Min Date Time
IA(A) 400.0 08/15/2001 14:00:36.676 15.6 08/15/2001 18:20:00.615
IB(A) 399.3 08/15/2001 14:00:36.726 19.6 08/15/2001 17:48:24.444
IC(A) 398.7 08/15/2001 14:00:36.676 19.1 08/15/2001 17:50:12.939
IN(A) 0.1 08/15/2001 17:53:21.805 0.1 08/15/2001 17:53:21.805
IG(A) 23.5 08/15/2001 15:44:54.574 1.5 08/15/2001 17:42:12.187
VAB(V) 470 08/15/2001 18:29:45.812 72 08/15/2001 18:28:49.100
VBC(V) 465 08/15/2001 15:33:17.710 200 08/15/2001 13:45:42.984
VCA(V) 464 08/15/2001 13:28:21.973 86 08/15/2001 13:45:43.971
VG(V) RESET RESET
kW3P 159.7 08/15/2001 14:00:36.755 0.0 08/15/2001 18:26:44.964
kVAR3P 15.7 08/15/2001 18:29:34.063 -0.0 08/15/2001 18:29:48.921
kVA3P 159.6 08/15/2001 14:35:26.772 2.3 08/15/2001 18:28:48.928
1 WDG (F) 161 08/15/2001 14:32:18.416 118 08/15/2001 04:44:36.676
2 WDG (F) 158 08/15/2001 14:33:26.356 124 08/15/2001 04:36:58.786
3 WDG (F) 155 08/15/2001 14:38:14.284 116 08/15/2001 04:42:32.476
4 WDG (F) 164 08/15/2001 14:31:34.676 128 08/15/2001 04:40:14.135
5 WDG (F) 150 08/15/2001 14:40:46.763 115 08/15/2001 04:39:28.616
6 WDG (F) 158 08/15/2001 14:36:33.656 121 08/15/2001 04:39:40.526
7 BRG (F) 120 08/15/2001 14:20:36.476 74 08/15/2001 04:45:34.873
8 BRG (F) 112 08/15/2001 14:18:58.067 78 08/15/2001 04:44:56.908
9 BRG (F) 114 08/15/2001 14:35:32.985 76 08/15/2001 04:35:46.089
10 BRG (F) 109 08/15/2001 14:30:16.975 81 08/15/2001 04:36:18.542
11 AMB (F) 98 08/15/2001 14:28:38.186 62 08/15/2001 04:38:36.458
LAST RESET 08/15/2001 11:09:10.745
=>
Figure 5.11
METER M Command Example.
Thermal & RTD Metering: METER T
The
METER T
command displays the temperatures of any connected RTDs. This
command also shows the motor current in % of Full Load Amps, the present thermal
model % Thermal Capacity, and the RTD % Thermal Capacity if ambient and winding
temperatures are monitored and a winding RTD trip temperature is set. If the motor is
Содержание SEL-701-1
Страница 16: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 34: ...This page intentionally left blank ...
Страница 118: ...This page intentionally left blank ...
Страница 142: ...This page intentionally left blank ...
Страница 196: ...This page intentionally left blank ...
Страница 210: ...This page intentionally left blank ...
Страница 242: ...This page intentionally left blank ...
Страница 384: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 452: ...This page intentionally left blank ...