Date Code 20011009
SEL-701-1 Monitor
ASCII Serial Port Operation
Command Explanations
5.21
=>>
PUL TRIP 1
Are you sure (Y/N) ? Y
=>>
Figure 5.13
PULSE Command Example.
QUIT (Level 2)
The
QUI
command returns the monitor to Access Level 1.
RLP (Level 2)
Use the
RLP
(Reset Learned Parameters) command at Access Level 2 to reset the
learned motor parameters. You can reset the learned motor stopped cooling time and
the learned motor starting time values individually. After a value is reset, the monitor
needs five motor starts or motor stops to learn the parameter. Only use this command
when the monitor is initially installed, after a motor rewind, or after overhaul of the
load equipment.
=>>
RLP
Reset the Learned Cooling Time (Y/N)? Y
Learned Cooling Time Reset
Reset the Learned Starting Thermal Capacity (Y/N)? Y
Learned Starting Thermal Capacity Reset
=>>
Figure 5.14
RLP Command Example.
SER (Level 1 or 2)
Use the
SER
(Sequential Events Record) command to view the Sequential Events
Recorder (SER) report, described in detail in
. Each event
record is stored with a record number, a date, and a time. You can access SER data by
record number or by date. The most recent record is always record number 1. The
various
SER
command options are shown in
.
Содержание SEL-701-1
Страница 16: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 34: ...This page intentionally left blank ...
Страница 118: ...This page intentionally left blank ...
Страница 142: ...This page intentionally left blank ...
Страница 196: ...This page intentionally left blank ...
Страница 210: ...This page intentionally left blank ...
Страница 242: ...This page intentionally left blank ...
Страница 384: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 452: ...This page intentionally left blank ...