9
P40-R I&O Manual
IM120801
RD: AUG 2013
RL: 1D
Calculate Maximum Stack Height ‘
H
’: (Enter value ‘
H
’ on the peel and stick label supplied)
53 inches (135 cm) is the required minimum clearance below the heater (‘
C
’)
‘T’ is measured on site = distance from the bottom of the heater hanger to the floor
H
= T- 53 inches (135 cm): Do not stack or store higher than ‘
H
’ under the heater
Do not place or store materials or shelving within the Clearance to Combustibles Box
represented by the dotted lines in Figure 2 above
H
Suspended at an
angle up to 30°
Suspended
Horizontally
T
T
FLOOR
FLOOR
H
E:
24” (61 CM) FROM ‘U’ TUBE END
*The clearance to combustible materials represents the minimum distance that must be main-
tained between the heater and a nearby surface.
The stated clearance to combustibles
represents a surface temperature of 117F° (65C°) above room temperature.
It is the installer’s responsibility to ensure that building materials with a low heat toler-
ance which may degrade at lower temperatures are protected to prevent degradation.
Examples of low heat tolerance materials include vinyl siding, fabrics, some plastics,
filmy materials, some coatings and laminated finishes, etc.
TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLE SURFACES OR MATERIALS*
MODELS
SUSPENDED
HORIZONTALLY
SUSPENDED AT AN ANGLE
UP TO 30 DEGREES
P40-R
A:
TOP
inches (cm)
C:
BELOW
inches (cm)
S:
SIDES
inches (cm)
A:
TOP
inches (cm)
C:
BELOW
inches (cm)
F:
FRONT
inches (cm)
B:
BACK
AT 30°
inches (cm)
5
(12.7)
53
(135)
24
(61)
5
(12.7)
53
(135)
36
(91.5)
12
(30.5)
E:
‘U’
END
of heater :
24”
(61 cm)
(horizontal or angled)
B:
BACK
< 30°
inches (cm)
24
(61)
Clearance to Combustibles box
around the heater
FIGURE 2 MINIMUM CLEARANCES TO COMBUSTIBLES* END VIEW - See Table 1 above