16
P40-R I&O Manual
IM120801
RD: AUG 2013
RL: 1D
5. Install the structural fastening hardware and any suspension hardware (chain, etc) prior to
removing heater from the carton. Ensure that the support hardware system is firmly fas-
tened to a structural member(s) of sufficient strength and integrity to support the weight of
the heater.
6. The heater comes fully assembled from the factory. For locations where there is con-
strained access for installation, removal of the burner assembly may assist in the installa-
tion of the tube/reflector assembly. Disconnect the spark wire from the igniter and remove
the four nuts that fasten the burner to the tube flange. Re-install the burner after the tube
system is installed. If the tube/reflector system is to be oriented up to a 30° mounting angle
(see below), the burner must be adjusted to a horizontal operating position.
Up to 30° Angle Mounting:
7. The tube/reflector system can be oriented on the short axis from horizontal to an angle up
to 30 degrees. When angle mounted the vent side of tube must always be higher than the
burner side. The tube/reflector system must be level along its length
8. When the tube/reflector is suspended at an angle up to 30°, the burner mounting flange has
a slot pattern that allows adjustment (rotation) of the burner to a horizontal position for
proper operation (see Figure 4 below, and Figure 6 next page).
Install the tube/reflector system as above, with tube/reflector assembly angled up to 30°
Loosen the 4 nuts (2 or 3 turns) until burner studs can rotate in the flange slots
Ensure that the gasket between burner and flange rotates with the burner
Tighten the 4 nuts to secure the burner in the horizontal position
9. For seismic and high wind restraint see Sections 10-A & 10-B, page 18.
FIGURE 4 HEATER SUSPENSION: HORIZONTAL TO 30° ANGLE