Operation Manual Flow Transmitter DW-D 

1.

MOUNTING 

1.1    Position of mounting 

It is advantageous to install the unit in a straight piece of pipe and to choose a place of 

mounting which has the biggest possible distance from elbows, valves etc.  

It is especially important to have the biggest possible distance from magnet valves and ball 

valves. Please make sure that they are opened as slow as possible, especially if the pipe after 
the valve is empty. These measures prevent the measuring system from flow shocks which 
can cause damages. We recommend a straight length of 10 

 d at input side and 5 

 d at the 

output side (d= diameter of pipe). 

The apparatus provides a stable signal when installed at closer distances, but depending on 

flow conditions it may be less accurate 

 

1.2  Mounting position on electronic view

 

Please take in consideration that the mounting has to be done EMI conform in order to avoid 

interruptions of operations. 

Especially the following points have to be attended: 
- The provided ferrites have to be mounted as described. 
- Signal and supply cable of the DW-D may not directly taken close to 230V or 380V wirings. 
- The device should not be installed close to inductance, switching loads, engines or similar 

sources of inductive fields. 

 

1.3  Direction of Flow

 

 

It is essential that the unit is mounted so that flow is as indicated by the arrow on the body. 
The unit will not operate unless installed correctly in this way and the possibility of damage to 
the unit cannot be excluded. 

 

1.4   Mounting Orientation

 

 

If the display has to be changed to a new position, it is possible to turn it relative to the 
housing. To do this, remove the front and back of the housing and remove the screw retaining 
the electronic board to the housing. Rotate the electronic board to the new desired position 
taking care not to damage the cable link, refit and secure the retaining screws. In a similar 
way, the window on the front of the access cover can also be turned. 

 

2.     MOUNTING AT THE TUBE

 

2.1  Items with THREAD CONNECTION

 

 

We recommend sealing all threads with PTFE sealing tape. Ensure no excess of tape is left 
protruding into the pipe. 

 

When screwing the unit into a pipe, take care to ensure that the housing is not damaged or 
impacted during the process. 

   

2.2  Items with FLANGE CONNECTION

 

 

An approved flange seal or gasket must be used. Neither this nor the required fixing bolts are 
included in the delivery. Ensure the transmitter is not damaged when tightening the flange 
bolts. 

 

Содержание DW-D

Страница 1: ...the DW D may not directly taken close to 230V or 380V wirings The device should not be installed close to inductance switching loads engines or similar sources of inductive fields 1 3 Direction of Flow It is essential that the unit is mounted so that flow is as indicated by the arrow on the body The unit will not operate unless installed correctly in this way and the possibility of damage to the u...

Страница 2: ...cket to the pipe Mount the flow transmitter to the socket ensuring that the pendulum is not damaged during this procedure Align the transmitter into the final desired position before tightening the union nut A Please do not forget to keep the flow direction in consideration before weld on the socket groove 2 4 Torsional moment of the union nut If the device shall be divided from the t piece or the...

Страница 3: ...de of the enclosure The button P has the function to choose a point of the menu and to take over the wished values With the buttons and you can set a value Button increases value Button decreases the value Pressing this button one time the value changes for one digit If you keep the buttons on hold the value is changing continuously After some time velocity is increasing At some points of the menu...

Страница 4: ...ting the switch point of RELAIS 1 is now completed Actuate P button once more causes changing to RELAIS 2 Adjustment is like described under RELAIS 1 When the adjusted value is reached a lamp glows for control The green one A is assigned to RELAIS 1 the red one to RELAIS 2 B 4 3 Adjusting of output occupancy DW D comes with current voltage and frequency output The different output types only can b...

Страница 5: ...present at the time of power failure This guarantees that the operator is aware of that power supply was interrupted and so the amount indicated perhaps not corresponds to the real quantity Attention The power failure supervising function only works if at menu point BATT CHECK see 4 1 the function is activated ON The device has a 8 digit display so a big capacity is available Nevertheless dependin...

Страница 6: ...put impermissible values will normally be transferred These are 1mA 20V respectively 0 Hz In order to re establish the function of the item in such a case the necessary software is saved additionally for safety reasons The software can be load again with the menu item FACTORY RESET Therefore push the button or in the menu FACTORY RESET You will be asked to start the action Y button or to break up ...

Страница 7: ...oy the calibration Clean the pendulum system before re installing into the pipe IMPORTANT If the DW D must be separated from the tee loosen nut A and cant the unit a little opposed to direction of flow Then lift the DW D with pendulum rectangular out of the tee Please perform all disassembly reassembly operations with great care Avoid damage Especially to the pendulum system 6 TECHNICAL DATA Power...