Operation Manual Flow Transmitter DW-D 

4.8   Programming the interface

 

 

Under point of menu 

DWD ADR:

 the address of each device can be programmed (selection 

by 

, input by  P). For more details please see our data sheet for devices with interface. It is 

only added to devices which are equipped with this option. (Also see point 3.5)  

 
4.9

 

Mounting the ferrite

 

 

The HSW flow transmitter DW-D is EMI certified and comes up to the corresponding norm. 
The EMI directive will only be achieved, if the provided ferrites are mounted as mentioned 
under 3.1 3.2 3.33 and 3.4. If not, serious malfunctions can be appeared depending on the 
mounting position. (q.v. 1.2) 

 

IMPORTANT! Always mount the ferrite

 

 

 

4.10  Protection on data loss

 

 

If your device is operated on incorrect EMI conditions, it could come to data loss respectively 
damages of coded data in extreme cases. 

 

As the item need these data for a correct function there hereby is an anticipate protection. 

 

In this case the item is showing 

K DATA MISSING

 

So that this information is available for the occupant, even in case of a use of the analogue-
voltage or frequency output, impermissible values will normally be transferred. These are 
1mA, 20V, respectively 0 Hz. 

 
 

In order to re-establish the function of the item in such a case, the necessary software is 
saved additionally for safety reasons. The software can be load again with the menu item 

FACTORY RESET

. Therefore push the button

 or 

 in the menu 

FACTORY RESET

. You 

will be asked to start the action (Y) button 

 or to break up (N) button

 

ATTENTION! When starting the application, all adjusted data as switch points, totalizer 
value etc. will be lost. (Reset to the original factory setting)

 

 

 

 

Please consider this and keep the data before starting the procedure in mind. After the 
reestablishment has been started, you will get informed about the status of the procedure. 
When the flow indication on the display appears, the operation is over. The device is working 
as usual again. Please consider that e.g. the switch points have to be new installed again. 

 

We would like to point out, that the data loss occurs only if the item is used under forbidden 
conditions. Therefore it is really necessary to open corresponding arrangements in order to 
avoid a new data loss. 

 

This could be: mounting the provided ferrites, installation of the device at another position, 
changing the cabling within the installation (no measure or feed lines of the transmitter near 
high voltage feed cable). Reducing of radiation or magnetic field or even the installation of 
suitable electrostatic shields. 

 

 

 

 

 

   

 

 

 

 

Содержание DW-D

Страница 1: ...the DW D may not directly taken close to 230V or 380V wirings The device should not be installed close to inductance switching loads engines or similar sources of inductive fields 1 3 Direction of Flow It is essential that the unit is mounted so that flow is as indicated by the arrow on the body The unit will not operate unless installed correctly in this way and the possibility of damage to the u...

Страница 2: ...cket to the pipe Mount the flow transmitter to the socket ensuring that the pendulum is not damaged during this procedure Align the transmitter into the final desired position before tightening the union nut A Please do not forget to keep the flow direction in consideration before weld on the socket groove 2 4 Torsional moment of the union nut If the device shall be divided from the t piece or the...

Страница 3: ...de of the enclosure The button P has the function to choose a point of the menu and to take over the wished values With the buttons and you can set a value Button increases value Button decreases the value Pressing this button one time the value changes for one digit If you keep the buttons on hold the value is changing continuously After some time velocity is increasing At some points of the menu...

Страница 4: ...ting the switch point of RELAIS 1 is now completed Actuate P button once more causes changing to RELAIS 2 Adjustment is like described under RELAIS 1 When the adjusted value is reached a lamp glows for control The green one A is assigned to RELAIS 1 the red one to RELAIS 2 B 4 3 Adjusting of output occupancy DW D comes with current voltage and frequency output The different output types only can b...

Страница 5: ...present at the time of power failure This guarantees that the operator is aware of that power supply was interrupted and so the amount indicated perhaps not corresponds to the real quantity Attention The power failure supervising function only works if at menu point BATT CHECK see 4 1 the function is activated ON The device has a 8 digit display so a big capacity is available Nevertheless dependin...

Страница 6: ...put impermissible values will normally be transferred These are 1mA 20V respectively 0 Hz In order to re establish the function of the item in such a case the necessary software is saved additionally for safety reasons The software can be load again with the menu item FACTORY RESET Therefore push the button or in the menu FACTORY RESET You will be asked to start the action Y button or to break up ...

Страница 7: ...oy the calibration Clean the pendulum system before re installing into the pipe IMPORTANT If the DW D must be separated from the tee loosen nut A and cant the unit a little opposed to direction of flow Then lift the DW D with pendulum rectangular out of the tee Please perform all disassembly reassembly operations with great care Avoid damage Especially to the pendulum system 6 TECHNICAL DATA Power...

Отзывы: