Table 1: Diagnostic information of the safety switchgear
System condition
Magnet control IN
LED
Safety outputs Y1,
Y2
Diagnostic
output OUT
Power to
unlock
Power to
lock
green
red
yellow
AZM300Z
AZM300B
Safety guard open
24 V (0 V)
0 V (24 V)
On
Off
Off
0 V
0 V
0 V
Safety guard closed,
not
locked
24 V
0 V
On
Off
Flashes
0 V
24 V
24 V
Safety guard closed,
locking
impossible
0 V
24 V
On
Off
Flashes
0 V
24 V
0 V
Safety guard closed and
locked
0 V
24 V
On
Off
On
24 V
24 V
24 V
Error warning
1)
0 V
24 V
On
Flashes
2)
On
24 V
1)
24 V
1)
0 V
Error
0 V (24 V)
24 V (0 V)
On
Flashes
2)
Off
0 V
0 V
0 V
No input signal at X1 and/or
X2
0 V (24 V)
24 V (0 V)
Flashes
Off
Off
0 V
0 V
0 V
No input signal at X1 and/or
X2
0 V (24 V)
24 V (0 V)
Flashes
Off
On/Flashes
0 V
0 V
24 V
Additionally for variant I1/I2:
Teach-in procedure actuator
started
Off
Off
Flashes
0 V
0 V
0 V
Only I2: teach-in procedure
actuator (release block)
Flashes
Off
On
0 V
0 V
0 V
1)
after 30 min: disabling due to fault
2)
refer to flash code
Table 2: Error messages / flash codes red diagnostic LED
Flash pulses
(red)
Designation
Autonomous switch-off
after
Error cause
1 flash pulse
Error (warning) at output Y1
30 min
Fault in output test or voltage at output Y1, although the
output is disabled.
2 flash pulses
Error (warning) at output Y2
30 min
Fault in output test or voltage at output Y2, although the
output is disabled.
3 flash pulses
Error (warning) cross-wire
short
30 min
Cross-wire short between the output cables or fault at
both outputs
4 flash pulses
Error (warning) temperature
too high
30 min
The temperature measurement reveals an internal
temperature that is too high
5 flash pulses
Actuator fault
0 min
Incorrect or defective actuator, bracket broken
6 flash pulses
Fault rotary handle
0 min
Rotary handle not in authorised intermediate position
Continuous red
signal
Internal error
0 min
Device defective