IO Link Data Dictionary
SCPMi
21.10.01.00125
14.06.2019
J. Schmalz GmbH
Johannes Schmalz Str. 1, D 72293 Glatten
Tel.: +49(0)7443/2403 0
Fax: +49(0)7443/2403 259
[email protected]
32
0x0020
0
2 bytes
ro
Number of errors since last power up
36
0x0024
0
1 byte
ro
0 = Device is operating properly
1 = Maintenance required
2 = Out of specification
3 = Functional check
4 = Failure
37
0x0025
0
96 bytes
ro
Information about currently pending events
Fixed length array format according to IO Link specification V1.1
130
0x0082
0
2 bytes
ro
Bit 00: Internal error: data corruption (E01)
Bit 01: reserved
Bit 02: Primary voltage too low (E07)
Bit 03: Primary voltage too high (E17)
Bit 04 07: reserved
Bit 08: short circuit at OUT2 (E12)
Bit 09 10: reserved
Bit 11: Measurement range overrun (FFF)
Bit 12 14: reserved
Bit 15: IO Link communication interruption (E08)
138
0x008A
1
1 byte
ro
Type code of active device status (see below)
138
0x008A
2
2 bytes
ro
ID code of active device status (see below, corresponds to IO Link events)
139
0x008B
0
1 byte
ro
Result of recent NFC activity:
0x00: Data valid, write finished successfully
0x23: Write failed: Write access locked
0x30: Write failed: parameter(s) out of range
0x31: Write failed: parameter value too high
0x32: Write failed: parameter value too low
0x41: Write failed: parameter set inconsistent
0xA1: Write failed :invalid authorisation
0xA2: NFC not available
0xA3: Write failed: invalid data structure
0xA5: Write pending
0xA6: NFC internal error
146
0x0092
0
2 bytes
ro
Bit 0: Valve protection active
Bit 1: Evacuation time t1 above limit [t 1]
Bit 2: Leakage rate above limit [ L ]
Bit 3: SP1 not reached in suction cycle
Bit 4: Free flow vacuum > rP2 but < SP1
Bit 5: Primary voltage US outside of optimal range
Bit 6: reserved
Bit 7: reserved
Bit 8: Input pressure outside of operating range
Bit 9 15: reserved
155
0x009B
0
1 byte
ro
Air consumption of last suction cycle (unit: 1 %)
156
0x009C
0
2 bytes
ro
Air consumption of last suction cycle (unit: 0.1 Nl)
157
0x009D
0
2 bytes
ro
Energy consumption of last suction cycle (unit: 1 Ws)
162
0x00A2
0
1 byte
ro
Quality of last suction cycle (unit: 1 %)
163
0x00A3
0
1 byte
ro
Last measured performance level (unit: 1 %)
IO Link
Display Code
Remark
Event Type
hex
hex
0x0000
0x10
(no IOL event)
Device is working optimally
0x1811
0x82
Error
E01
Internal error, user data corrupted
0x8C20
0x81
Error
FFF
Measured vacuum value too high, sensor fault
0x0999
0x81
(no IOL event)
E08
IO Link communication is interrupted (readable via NFC)
0x5100
0x42
Error
E07
Primary supply voltage (US) too low
0x5110
0x42
Warning
E17
Primary supply voltage (US) too high
0x1802
0x42
Warning
Input pressure too high or too low
0x180C
0x22
Warning
Condition Monitoring: primary supply voltage US outside of operating range
0x1807
0x22
Warning
Condition Monitoring: valve has switched too fast, continuous
suction activated
0x1808
0x21
Warning
Condition Monitoring: evacuation time t1 is above limit [t 1]
0x1809
0x21
Warning
Condition Monitoring: leakage rate is above limit [ L ]
0x180A
0x22
Warning
Condition Monitoring: vacuum level SP1 was never reached during
suction cycle
0x180B
0x21
Warning
Condition Monitoring: free flow vacuum above SP2
0x8C01
0x21
Warning
Manual mode is active
0x1800
Notification
Calibration offset 0 set successfully
0x1801
0x22
Notification
E03
Sensor value too high or too low, offset not changed
0x1817
Notification
Permissible leakage and permissible evacuation time have been set
automatically for the active profile
0x1818
Notification
Handling of the part is complete (neutral state of vacuum system reached
or new suction phase begun)
0x7710
0x41
Error
E12
output is connect with counterpotential
30480
Critical condiction, low
short circuit at OUT2
Data Corruption
Handling Cycle Completed
Primary supply voltage over run
IO Link communication interruption
CM: leakage rate above limit
Autoset completed successfully
Measurement range overrun
Vacuum calibration OK
Vacuum calibration failed
Supply pressure fault
CM: free flow vacuum too high
Primary supply voltage out of optimal range
Simulation active
CM: SP1 not reached
General power supply fault
CM: Valve protection active
CM: evacuation time above limit
Active Errors
Coding of Extended Device Status (ISDU 138) and IO Link Events
dec
NFC Status
Extended Device Status Type
Extended Device Status ID
Predictive Maintenance [PM]
Performance
Error Count
IO Link Device Status
Device Status
Condition Monitoring [CM]
Diagnosis
6168
35841
6151
6152
6153
6155
6167
6144
6154
Critical condiction, high
Air consumption per cycle in percent
Air consumption per cycle
Energy consumption per cycle
Quality
Energy Monitoring [EM]
(IOL event only)
Warning, low
Warning, high
Warning, low
Warning, low
Defect/fault, high
Defect/fault, lower
(IOL event only)
Warning, high
Warning, high
(IOL event only)
20736
20752
6146
6145
Warning, high
Critical condiction, high
6156
Critical condiction, high
Warning, low
2457
Event name
0
Everything OK
Everything OK
Extended Device Status ID
Meaning
6161
35872
Detailed Device Status
Condition monitoring
(= IO Link Event Code)
Defect/fault, lower
Extended Device Status Type
J. Schmalz GmbH
3 of 3