background image

E X P L O S I O N P R O O F

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

ExMax-S-F1_en

V07 – 19-Oct-2021

ExMax-...-F1 

ExMax-...-SF1 

 ExMax-...-BF1

Special options 

... -CTS 

... -VAS

Important information for installation and operation

Extra information (see additional data sheet)

Additional technical information, dimensions, installation intruction, illustration 

and failure indication

A.  Installation, commissioning, maintenance

All national and international standards, rules and regulations for hazardous Ex-areas 

must be complied with. Certified apparatus must be installed in accordance with manufacturer 

instructions. If the equipment is used in a manner not specified by the manufacturer, the 

safety protection provided by the equipment may be impaired. For electrical installations 

design, selection and erection, EN/IEC 60079-14 can be used. 

For electrical connection an Ex-e terminal box is required (e.g. ExBox-...). 

Attention:

 If the actuator is put out of operation all Ex rules and regulations must be 

applied. You have to cut the supply voltage before opening the terminal box! 

The cables of the actuator must be installed in a fixed position and protected against 

mechanical and thermical damage. Connect potential earth. Avoid temperature transfer 

from armature to actuator! Close all openings with min. IP66. 

For outdoor installation a protective weather shield against sun, rain and snow should be 

applied to the actuator as well as a constant supply at terminal 1 and 2 for the integrated 

heater. During commissioning apply a self adjustment drive.

Actuators are maintenance free. An annual inspection is recommended. For electrical 

installations inspection and maintenance, EN/IEC 60079-17 can be used. Ex-actuators 

must not be opened by the customer.

B.  Manual override

Manual override only if supply voltage is cut. Use delivered socket wrench with slow 

motions, usage can be tight.

Attention:

 Releasing or letting go the Allen key too fast at manual operating actuators 

with spring return causes risk of injury!  

C.  Shaft connection, selection of running time

Actuators are equipped with a direct coupling double square shaft connection of 12 × 12 mm. 

For round shafts adaptors/clamping connection (accessories, e.g. KB-S) are available. 

The housing of the actuator is axially symmetrically built to select Open-close direction 

of the spring return function by left-right mounting. Using the 10-position switch different 

motor running times and spring return running times can be selected on site in acc. to 

the actuator type.

D.  Temperature trigger ...Pro-TT-...

The actuator ...Max-...-BF1 will work only with the temperature trigger ExPro-TT-...

E.  Operation with 3 sec. motor running time

Note following:

1.  The 3 sec. motor running time mode is only available in switch position 0 and 5 and 

at a constant supply voltage applied for a minimum of 1 minute on terminal 1 and 2. 

2.  The actuator opens at voltage on terminal 3 (resp. closes) and closes at voltage on 

terminal 4 (resp. opens) – depending on mounting position of the actuator.

3.  The max. duty ratio is 10 % resp. 1 cycle/minute. Between two fully 3 sec. cycles in 

the same direction there must be a minimum intermission of 1 minute. Trying to run 

the actuator in the same direction in less than the required minimum of 1 minute the 

function will be blocked for the rest of the idle period. Later the release for the next 

cycle is made automatically by an internal timing relay. 

4.  Same function is applied on spring return actuators, fail safe operation is regarded 

same as a motor running cycle. 

5.  Trying to use the 1 wire On-off methode in switch position 0 and 5, software changes 

the motor running time temporarily and automatically to 15 s/90° to protect the actuator 

for overheating due to uncontrolled duty ratio.

F.   Spring return

Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the 

event of an electrical interruption, the spring returns to its end position even if supply 

voltage is available again during return function. Thereafter operation will continue. 

G.  Operation at ambient temperatures below −20 °C

All actuators are equipped with a regulated integrated heating device designed for 

employments down to 

40 °C ambient temperature. The heater will be supplied automatically 

by connecting the constant voltage supply on the clamps 1 and 2. 
1.  After mounting the actuator must be immediately electrically connected.

2.  The heater switches on automatically when actuator reaches internally 

20 °C. It 

heats up the actuator to a proper working temperature, then heater switches off 

automatically. Actuator will not run during heating process.

3.  The adjustment options are only ensured after this heating up period. 

H.  Excess temperatures

In acc. to the ATEX rules and regulations Ex actuators must be protected against excess 

temperature. The internal thermostat works as a maximum limiter and, in the event of 

failure at incorrect temperatures, shuts off the actuator irreversible. An upstream connected 

temperature sensor stops the actuator before reaching its max. temperature. This safety 

feature is reversible, after cooling down the actuator is completely functional again. In 

this case the failure must be eliminated immediately on site!

I.   Synchron mode

Do not connect several actuators to one shaft or link mechanically together.

J.  Mechanical protection

Actuators must be operated with a minimum external load.

After installing the actuator to the damper/armature a self adjustment drive has to be 

performed in order to protect the damper/armature against mechanical overload.

During operation the actuator reduces briefly its speed (motor power) before reaching 

the end position for a “gentle” blockade/stop.

K.  Intrinsically safe circuits

The actuator has a flameproof enclosure acc. to EN 60079. The supply of the push 

button (adjustment drive), the 10-position switch (adjustment of torque and running time), 

the LED indicator  and the sensor connection ExPro-TT is performed intrinsically safe!

L.  Routine tests of fire dampers

For periodic inspection of fire dampers cut off the supply line (current of actuator).

The test button at ExPro-TT-... is only used for test purposes of actuator’s function.

Special solutions and accessories

...-CTS

 

Types in aluminium housing with seawater resistant coating

...-VAS

 

Types in stainless steel housing, parts nickel-plated 

Adaptions

  for dampers and valves on request 

ExMax-...-S3

  Ambient temperature up to +60 °C (T4), 110...240 VAC/DC, 25 % ED

ExPro-TT-...

  Safety temperature trigger for fire dampers

ExBox-...

 

Ex-e terminal boxes for zone 1, 2, 21, 22

MKK-S

 

Mounting bracket for boxes type ...Box-... directly on actuator

ExSwitch

 

2 external aux. switches, adjustable for zone 1, 2, 21, 22

KB-S

 

Clamp for damper shafts Ø 10...20 mm and 

 10...16 mm

AR-12-xx

 

Reduction part for 12 mm square connection to 11, 10, 9 or 8 mm shafts

BSH-S

 

Mounting holder for actuators in fire danger areas

Kit-S8

 

Cable glands nickel-plated

4 / 4

Содержание ExMax CTS Series

Страница 1: ...design and small dimension L W H 210 95 80 mm Direct coupling to the damper shaft with double square connection 12 12 mm 95 angle of rotation inclusive 5 pretension Robust aluminium housing optional with seawater resistant coating or in stainless steel IP66 protection Simple manual override included preparation for comfortable manual override Gear made of stainless steel and sinter metal Weight on...

Страница 2: ...x Imax AC 250 V 5 A Umin AC DC 5 V After one time operation with U 24 V AC DC or I 100 mA Umin AC DC 12 V Umax Imax DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 12 12 mm direct coupling 100 overload protected Electrical connection Cable 1 m wire cross section 0 5 mm equipotential bonding 4 mm Connections in hazardous areas require an Ex e terminal box Diameter o...

Страница 3: ... switches were operated with higher voltage or current Ex i intrinsic safe data for temperature trigger ExPro TT T 1 0 On off SB 2 4 On off 1 wire SB 2 5 Wiring of integrated auxiliary switches SB 3 2 On off spring return Ex i tripping circuit SB 7 4 Ex i tripping circuit for ExPro TT safety temperature trigger Test button Attention At 1 wire control mode the heater does not work in case of open c...

Страница 4: ...est of the idle period Later the release for the next cycle is made automatically by an internal timing relay 4 Same function is applied on spring return actuators fail safe operation is regarded same as a motor running cycle 5 Trying to use the 1 wire On off methode in switch position 0 and 5 software changes the motor running time temporarily and automatically to 15 s 90 to protect the actuator ...

Отзывы: