ExMax-S-F1_en

V07 – 19-Oct-2021

ExMax-...-F1 

ExMax-...-SF1 

 ExMax-...-BF1

Special options 

... -CTS 

... -VAS

Torque motor (min.)

 

8 Nm  

 

15 Nm 

 

8 resp. 15 Nm 

8 resp. 15 Nm

Torque spring (F)

 

min. 8 Nm 

 

min. 15 Nm 

 

min. 8 resp. 15 Nm 

min. 8 resp. 15 Nm

Torque blockade

 

In blockade and end positions torques are higher than above specified torques for motor and spring.

Dimensioning of external load

 

Upon spring return the external load should be max. 80 % of torque spring (F), but 

 

min. 2 Nm 

 

min. 5 Nm 

 

min. 2 resp. 5 Nm 

min. 2 resp. 5 Nm

Supply voltage / frequency

 

24...240 VAC/DC ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %

Power consumption

 

max. starting currents see 

Extra information (in acc. with voltage, I

 start

 >> I

 rated 

), approx. 5 W holding power, approx. 16 W for heater

Protection class

 

Class I (grounded)

Angle of rotation and indication

 

95° incl. ~ 5° pretension, mechanical value indication

Working direction

 

Selectable by left/right mounting to the damper/valve shaft

Motor running times

 

3 / 15 / 30 / 60 / 120 s/90° selectable on site

3 sec. mode – motor

 

In acc. with the supply voltage and external torque 3 to 4 s/90° angle of rotation

Motor

 

Brushless DC motor  

Control mode

 On-off

Spring return (F)

 

Spring return upon voltage interruption or opening of line 3, response time up to 1 sec. after voltage interruption

Spring return running time (F)

 

~ 1 s/90° (at temperatures below -20 °C, depending on the load, the spring return period can be up to 20 s.)

Safety operations at 1 sec. (F)

 

min. 1,000 acc. to construction of damper and ambient. Consider minimum external load!

Ex-i tripping circuit                ...-BF1

  Intrinsically safe circuit to connect the ExPro-TT-... safety temperature trigger directly to the actuator with M12 quick connection

Aux. switches            ...-SF1, ...-BF1 

2 integrated auxiliary switches, switching at 5° and 85° angle of rotation, potential free. Grid fuse-protection is recommended!

 U

max

/ I

max

 AC = 250 V/5 A;   U

min

 AC/DC = 5 V;  

After one-time operation with U > 24 V AC/DC or I > 100 mA:   U

min

 AC/DC =  12 V

 U

max

/ I

max

 DC =   48 V/1 A;    I

min

 AC/DC = 5 mA; 

  

 

 I

min

 AC/DC = 100 mA

Axle of the actuator

 

Double square 12 × 12 mm, direct coupling, 100 % overload protected

Electrical connection

 

Cable ~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm².

 

Connections in hazardous areas require an Ex-e terminal box!

Diameter of cable

 

~ Ø 6.2  mm 

 

~ Ø 6.2  mm   

~ Ø 6.2 + 7.4 mm  

~ Ø 9.3  mm 

 

2 cables in version ...-SF1 

Cable gland

 

M16 × 1.5 mm

Manual override

 

Use delivered socket wrench, max. 4 Nm 

Heater

 

Integrated, controlled heater for ambient temperature down to −40 °C

Housing material

 

Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTS) or stainless steel housing, 

 

 1.4581 / UNS-J92900 / similar AISI 316Nb (...-VAS)

Dimensions (L × W × H)

 

210 × 95 × 80 mm, for diagrams see 

Extra information

Weight

 

~ 3,5 kg aluminium housing, stainless steel ~ 7 kg

Ambients

 

Storage temperature −40…+70 °C, working temperature −40…+40 °C at T6 and −40…+50 °C at T5

Humidity

  

0...90 % rH, non condensing

Operating   3 sec. motor run time 

In 3 s mode the motor will work only after 1 minute of voltage supply. While open/close operation (open voltage supply and shut it down) 

 

motor works only with speed of 15 s/90°

               

 15 sec. motor run time

 at 

15 / 30 / 60 / 120 s 100 % of ED is permitted (ED = duty cycle)

Maintenance

 

Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations 

Wiring diagrams

 

SB 2.4/2.5  

SB 2.4/2.5  

SB 

2.4/2.5 + 3.2 

SB 2.4/2.5 + 7.4

Scope of delivery

 

Actuator, 4 screws M4 × 100 mm, 4 nuts M4, Allen key for simple manual override

Parameter at delivery

 

8 Nm, 30 s/90° 

 

15 Nm, 30 s/90° 

8 resp. 15 Nm, 30 s/90° 

8 resp. 15 Nm, 30 s/90°

Approbations

Technical data 

ExMax- 8 - F1 

ExMax- 15 - F1 

ExMax-... - SF1 

ExMax-... - BF1

ATEX Directive

 

 2014/34/EU

EU-Type Examination

    EPS 17 ATEX 1 132 X

IECEx Conformity

 

  IECEx EPS 17.0065X

Marking Gases

 

  II 2 (2) G    Ex db [ib Gb] IIC T6, T5 Gb

 

Types ...-CTS  II 2 (2) G    Ex db [ib Gb] IIB T6, T5 Gb

Marking Dusts

 

  II 2 (2) D    Ex tb [ib Db] IIIC T80°C, T95°C Db

Ex-i circuit data

 

  see table (T 1.0) 

CE Marking

 

  CE 0158 

EMC Directive 

 

2014/30/EU

Low Voltage Directive

  2014/35/EU

Enclosure Protection

    IP66 in acc. with EN 60529

2 / 4

Содержание ExMax CTS Series

Страница 1: ...design and small dimension L W H 210 95 80 mm Direct coupling to the damper shaft with double square connection 12 12 mm 95 angle of rotation inclusive 5 pretension Robust aluminium housing optional with seawater resistant coating or in stainless steel IP66 protection Simple manual override included preparation for comfortable manual override Gear made of stainless steel and sinter metal Weight on...

Страница 2: ...x Imax AC 250 V 5 A Umin AC DC 5 V After one time operation with U 24 V AC DC or I 100 mA Umin AC DC 12 V Umax Imax DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 12 12 mm direct coupling 100 overload protected Electrical connection Cable 1 m wire cross section 0 5 mm equipotential bonding 4 mm Connections in hazardous areas require an Ex e terminal box Diameter o...

Страница 3: ... switches were operated with higher voltage or current Ex i intrinsic safe data for temperature trigger ExPro TT T 1 0 On off SB 2 4 On off 1 wire SB 2 5 Wiring of integrated auxiliary switches SB 3 2 On off spring return Ex i tripping circuit SB 7 4 Ex i tripping circuit for ExPro TT safety temperature trigger Test button Attention At 1 wire control mode the heater does not work in case of open c...

Страница 4: ...est of the idle period Later the release for the next cycle is made automatically by an internal timing relay 4 Same function is applied on spring return actuators fail safe operation is regarded same as a motor running cycle 5 Trying to use the 1 wire On off methode in switch position 0 and 5 software changes the motor running time temporarily and automatically to 15 s 90 to protect the actuator ...