ExMax - ... - F1

ExMax - ... - SF1

ExMax - ... - BF1

ExMax -  ...  - CTS

ExMax -  ...  - VAS

ExMax-...-F1

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

ExMax-S-F1_en

V07 – 19-Oct-2021

Subject to change!

Compact. Easy installation. Universal. Cost effective. Safe.

Product views and applications

Description

Highlights

Safety damper

Ball valve

Throttle valve

Electrical, explosion proof rotary actuators with integrated Ex-i circuit (optional)

On-off control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension

8 Nm, 15 Nm with safety operation: fast spring return ~ 1 s*

ATEX tested in acc. with directive 2014/34/EU for zone 1, 2, 21, 22

Type 

Torque  

Supply 

Motor running time   

Spring return*   Control mode  Feedback 

Wiring diagram

ExMax-   8 - F1

 

  8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° 

On-off 

 

  – 

SB 2.4/2.5

ExMax- 15 - F1

 

15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° 

On-off 

 

  – 

SB 2.4/2.5

ExMax-   8 - SF1

    8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off 2 × aux. switches 

SB 2.4/2.5 + 3.2

ExMax- 15 - SF1

  15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off 2 × aux. switches 

SB 2.4/2.5 + 3.2

ExMax-   8 - BF1

    8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off 2 × aux. sw Ex-i tripping circuit  SB 2.4/2.5 + 7.4

ExMax- 15 - BF1

  15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off 2 × aux. sw Ex-i tripping circuit  SB 2.4/2.5 + 7.4

ExMax-  ...  - CTS

  Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)

ExMax-  ...  - VAS

  Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)

ExMax

  ¼ turn actuators  –  

size S

 For all types of gases, mists, vapours and dusts in zones 1, 2, 21 and 22

 Universal supply unit from 24…240 VAC/DC

5 different motor running times 3–15–30–60–120 s/90°, adjustable on site

 On-off control with fast spring return function

 Ex-i circuit for direct connection of the ...Pro-TT-... safety temperature trigger 

(type ...-BF1)

 2 integrated auxiliary switches, switching at 5° und 85° (type ...-SF1 and ...-BF1)

 100 % overload protected

 Compact design and small dimension (L × W × H = 210 × 95 × 80 mm) 

 Direct coupling to the damper shaft with double square connection 12 × 12 mm

 95° angle of rotation inclusive 5° pretension

 Robust aluminium housing (optional with seawater resistant coating) or in stainless steel

 IP66 protection

 Simple manual override in preparation for comfortable manual override

 Gear made of stainless steel and sinter metal

 Weight only ~ 3,5 kg

 

Integrated heater for ambient temperatures down to −40 °C 

 Integrated safety temperature sensor 

 Integrated equipment for manual adjustment (push button, lamp, switch)

 Preparation for adaptable and adjustable auxiliary switches type ...Switch

The ExMax actuators are a revolution for safety, control and shut-off 

dampers and other motorized applications for HVAC systems in chemical, 

pharmaceutical, industrial and offshore/onshore plants, for use in Ex-areas 

zone 1, 2 (gas) and zone  21, 22 (dust).

Highest protection class (ATEX) and IP66 protection, small dimensions, 

only 3,5 kg weight, universal functions and technical data, an integrated 

heater and an optional stainless steel housing guarantee safe operation 

even under difficult environmental conditions. High quality brushless 

motors guarantee long life.

All actuators are programmable and adjustable on site. Special tools or 

equipment are not required. Motor running times are selectable on site. 

The integrated universal power supply is self adaptable to input voltages 

in the range of 24...240 VAC/DC. The actuators are 100% overload 

protected and self locking.

...Max-...-F1

 actuators are equipped with spring return fail safe function. 

Additionally the 

...Max-...-SF1

 and 

...-BF1

 actuators are equipped with 

2 integrated, potential free auxiliary switches each and 

...Max-...-BF1

 

comes with an intrinsically safe tripping circuit for connecting the ...Pro-TT-... 

safety temperature trigger. Standard shaft connection is a double square 

direct coupling with 12 × 12 mm. 

Different accessories are available to adapt auxiliary switches, terminal 

boxes or adaptions for ball valves and throttle valves and other armatures. 

* at temperatures below 

20 °C, depending on the load, the spring return period can be up to 20 sec. If fast spring return below 

20 °C is required, please contact our sales support.

  Please note that nominal values are also subject to tolerances.

1 / 4

Содержание ExMax CTS Series

Страница 1: ...design and small dimension L W H 210 95 80 mm Direct coupling to the damper shaft with double square connection 12 12 mm 95 angle of rotation inclusive 5 pretension Robust aluminium housing optional with seawater resistant coating or in stainless steel IP66 protection Simple manual override included preparation for comfortable manual override Gear made of stainless steel and sinter metal Weight on...

Страница 2: ...x Imax AC 250 V 5 A Umin AC DC 5 V After one time operation with U 24 V AC DC or I 100 mA Umin AC DC 12 V Umax Imax DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 12 12 mm direct coupling 100 overload protected Electrical connection Cable 1 m wire cross section 0 5 mm equipotential bonding 4 mm Connections in hazardous areas require an Ex e terminal box Diameter o...

Страница 3: ... switches were operated with higher voltage or current Ex i intrinsic safe data for temperature trigger ExPro TT T 1 0 On off SB 2 4 On off 1 wire SB 2 5 Wiring of integrated auxiliary switches SB 3 2 On off spring return Ex i tripping circuit SB 7 4 Ex i tripping circuit for ExPro TT safety temperature trigger Test button Attention At 1 wire control mode the heater does not work in case of open c...

Страница 4: ...est of the idle period Later the release for the next cycle is made automatically by an internal timing relay 4 Same function is applied on spring return actuators fail safe operation is regarded same as a motor running cycle 5 Trying to use the 1 wire On off methode in switch position 0 and 5 software changes the motor running time temporarily and automatically to 15 s 90 to protect the actuator ...

Отзывы: