E X P L O S I O N P R O O F

ExMax-  8 -...F1

 

ExMax-  15 -

...

F1

 

  8 Nm

15 Nm

 ▼

 3 

s/90° 

  15  s/90° 

 

30  s/90°

 

  60  s/90° 

  120  s/90° 

00

01

02

03

04

05

06

07

08

09

ExBox

S

T

a

a

a

+

~

+

~

+

~

+

~

~

~

~

~

PE

PE

PE

PE

1

1

1

1

2

2

2

2

3

3

3

3

PA

PA

PA

PA

4

1

7

4

5

2

6

3

8

5

9

6

< 5°

< 5°

> 85°

> 85°

1

2

°C

ExPro-TT

 

 

U < 90 V AC/DC  2 AT  10 AT

U > 90 V AC/DC  5 AT  10 AT

 

 

U < 90 V AC/DC  2 AT  10 AT

U > 90 V AC/DC  5 AT  10 AT

U

o

  =    5,88 V

 I

o

  =  24,75 mA

P

o

  =  37      mW

C

i

  =    0

 L

i

   =    0

 

IIC 

 IIB 

 IIA

L

o

  50 mH      50 mH      50 mH

C

o

 43 

μ

F 1000 

μ

F 1000 

μ

F

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

ExMax-S-F1_en

V07 – 19-Oct-2021

ExMax-...-F1 

ExMax-...-SF1 

 ExMax-...-BF1

Special options 

... -CTS 

... -VAS

Electrical connection

Parameters, adjustments and failure indication

Parameter selection

Functions, adjustments and parameters

Type

Running times

Position of switch (S)

Torques

Example: 

ExMax-15-BF1

Requested parameter: 

Torque 

15 Nm

Motor running time  30 s/90°

Result:

Switch position  

02

Installation

Ex area – 

zone 1, 2, 21, 22

Safe area

Supply * 

24...240 VAC/DC ± 10 %

* electrical wiring see diagrams

Switch – Push button – Lamp 

for adjustment 

(behind the blanking plug)

10-position switch (S)
Push button (T)
3-colour LED

All actuators are equipped with a universal supply unit working at a voltage range from 

24...240 VAC/DC. The supply unit is self adjusting to the connected voltage! 

The safety operation of the spring return function works if the supply voltage is cut or line 3 

opened. For electrical connection inside hazardous areas an Ex-e terminal box, certificated 

in acc. with ATEX is required (e.g. ExBox). 

An over-current protection fuse < 10 A has to be provided by installer. 

Note: the initial current is appr. 2 A for 1 second.

Integrated auxiliary switches signal the rotation angle’s position. U

min

 and I

min

 change once 

the switches were operated with higher voltage or current.

Ex-i intrinsic safe data – for temperature trigger ExPro-TT  T 1.0

On-off  

SB 2.4

On-off  (1 wire) 

SB 2.5

Wiring of integrated auxiliary switches 

SB 3.2

On-off  – spring Ex-i tripping circuit 

SB 7.4

Ex-i tripping circuit for 

ExPro-TT-... safety 

temperature trigger 

Test 

button

Attention!

At 1-wire control 

mode the heater 

does not work in 

case of open contact. 

24...240 VAC/DC

24...240 VAC/DC

24...240 VAC/DC

24...240 VAC/DC

Attention

During commissioning apply a self adjustment drive. 

Regard duty cycle at motor running times!

Never use spring return actuators without external load.

Auxiliary switches * 

see Technical data

Integrated auxiliary switches, 

Grid fuse-protection recommended. 

 

min. max.

Integrated auxiliary switches, 

Grid fuse-protection recommended. 

 

min. max.

A)  Self adjustment of angle of rotation 

ATTENTION:

 To adjust the angle of rotation connect only wire 1 and 2. 

Do not connect wire 3. 

Apply supply voltage to wire 1 and 2. Turn switch (S) to position 02. Press 

button (T) for a minimum of 3 seconds. The actuator drives to the first end posi-

tion, detects the blocking position and performs a spring return to the starting posi-

tion. The LED flashes GREEN during adjustment. After that disconnect from the 

mains and connect wire 3. 

The adjustment takes about 31 seconds (30 sec. “On”, 1 sec. “Off”).

B)  Selecting motor running time 

Adjust parameters only if actuator is in idle state or without applied potential. 

Turn switch (S) to the position required for the intended operation acc. to table 

above. The selected parameters will be carried out at the actuator’s next opera-

tion.  

C)  Function of the ExPro-TT-... in the Ex-i tripping circuit 

When the ...Pro-TT’s tripping circuit is opened the actuator runs into its end posi-

tion with spring return.

D)  Additional information for control in On-off operation 

a closed  

= actuator opens

a open  

= spring return

The rotation direction (clockwise/counter clockwise) depends on left/right 

mounting of the actuator to the damper. 

3 / 4

Содержание ExMax CTS Series

Страница 1: ...design and small dimension L W H 210 95 80 mm Direct coupling to the damper shaft with double square connection 12 12 mm 95 angle of rotation inclusive 5 pretension Robust aluminium housing optional with seawater resistant coating or in stainless steel IP66 protection Simple manual override included preparation for comfortable manual override Gear made of stainless steel and sinter metal Weight on...

Страница 2: ...x Imax AC 250 V 5 A Umin AC DC 5 V After one time operation with U 24 V AC DC or I 100 mA Umin AC DC 12 V Umax Imax DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 12 12 mm direct coupling 100 overload protected Electrical connection Cable 1 m wire cross section 0 5 mm equipotential bonding 4 mm Connections in hazardous areas require an Ex e terminal box Diameter o...

Страница 3: ... switches were operated with higher voltage or current Ex i intrinsic safe data for temperature trigger ExPro TT T 1 0 On off SB 2 4 On off 1 wire SB 2 5 Wiring of integrated auxiliary switches SB 3 2 On off spring return Ex i tripping circuit SB 7 4 Ex i tripping circuit for ExPro TT safety temperature trigger Test button Attention At 1 wire control mode the heater does not work in case of open c...

Страница 4: ...est of the idle period Later the release for the next cycle is made automatically by an internal timing relay 4 Same function is applied on spring return actuators fail safe operation is regarded same as a motor running cycle 5 Trying to use the 1 wire On off methode in switch position 0 and 5 software changes the motor running time temporarily and automatically to 15 s 90 to protect the actuator ...

Отзывы: