INSTALLATION INSTRUCTIONS
Jointing System
All joints in the ICID Plus chimney range, which require a locking band, are made by means of a simple twist lock
jointing method. This is achieved by pushing together the male and female collars on each end of the main chimney
components and twisting the components through 1/6 of a turn to lock the collars into place.
It should be noted that the female collars on elbows and tees are not barbed in order to allow for these items to be
positioned according to requirements on site. In all cases the joints should be held securely in place using the locking
band, which is supplied with all components with a female collar.
Standard Chimney Sections (Pipes,Tees and Elbows)
Before assembling chimney sections, loosen the locking band by lifting the clip. Push the interlocking collars together and
twist into position (see Fig.1). Position the locking band so that it grips both collars then fasten using the clip.
Note:-joints must NOT occur within floor or ceiling spaces.
All flue gas carrying components must be installed with the direction arrow on the product label pointing to termination
with the external male collar uppermost.
Locking Band
(supplied with each component with a female collar)
A locking band must be fitted to every joint in the system. The band is of stainless steel construction and is fitted with
a quick release clip.
Fig. 1
Without Lip Seal
ICID Plus for N rated
Negative Pressure
Applications
(i.e Stoves)
Fig. 2
With Lip Seal
ICID Plus for P rated
Positive Pressure
Applications
(i.e Condensing Boilers)
Stainless Steel Outer Case
Male Collar
Stainless Steel Inner Liner
Insulation
Inward Bead
Female Collar
Male Collar
Lubricant
Female Lip Seal
Inward Bead
YELL
OW P
ARAFFIN W
AX
DO NO
T SW
ALL
OW
Male Spigot