Adaptors from Prima Plus & Prima Smooth to ICID Plus
These components are used to convert from a single wall connecting flue pipe to the ICID Plus system chimney. The
protruding liner should be pushed down inside the female socket of the connecting flue pipe, with the male collar
pointing upwards.
Adaptor to Flex/TecnoFlex Plus
This component is used to convert from ICID Plus to Flex/TecnoFlex Plus.The Flex/TecnoFlex Plus is pushed down
inside the upstand on the adaptor, secured using self tapping screws and sealed with fire cement and fire rope to
provide a gas tight joint.
Adaptor from ICID Plus to Prima Plus
This component is manufactured with an ICID Plus female collar and a Prima Plus female socket, and is used where
there is a requirement to convert from ICID Plus to Prima Plus.The ICID Plus female collar should be attached to
the previous ICID Plus component and the joint secured using the locking band provided.
Adaptor from ICID Plus to Prima Smooth
This component is manufactured with an ICID Plus female collar and a Prima Smooth female socket, and is used where
there is a requirement to convert from ICID Plus to Prima Smooth. The ICID Plus female collar should be attached to
the previous ICID Plus component and the joint secured using the locking band provided.
Structural Locking Band
The structural locking band, which is purchased separately, is used instead of a standard locking band in a situation
where extra structural support is required, for instance where the chimney height is >1.5m above the last support or
above the roof. It is also used to provide extra support in long horizontal runs. A maximum of 3m unsupported height
can be achieved by fitting the structural locking band on the joint immediately below and on every joint above the last
support. Please see diagram on page 32.
Structural Locking Band for Bends
The structural locking band for Bend, which is purchased separately, is used instead of a standard locking band in a
situation where extra structural support is needed in an offset.
Appliance Connector
Male
Collar
Protuding
Liner
Appliance Connector
1.
2.
The protruding liner of these components should be pushed into the appliance
spigot with the male collar pointing upwards. The liner can be trimmed to suit
the depth of the appliance spigot.
On solid fuel appliances the appliance connector should be sealed to the
appliance with fire rope and fire cement or high temperature sealant to provide
a gas tight joint.