NBS – Fan coil unit
TECHNICAL DOCUMENTATION
Technical data
Construction subject to change.
No return possible.
Version: 06.05.21 | Page 28
NBS-100-3-L4-C5
v
motor
V
L
p
s
W
Q
T
Q
S
V
W
Δp
W
t
L2
V
K
Q
V
W
Δp
W
t
L2
(m³/h)
(Pa)
(W)
(kW)
(kW)
(l/h)
(kPa)
(°C)
(l/h)
(kW)
(l/h)
(kPa)
(°C)
p
s, max
5
907
160
244
6.98
4.99
1202
6.4
10.1
2.9
5.33
909
8.7
37.5
4
846
160
217
6.59
4.70
1134
5.8
10.0
2.7
5.05
862
7.9
37.8
3
773
160
198
6.10
4.34
1051
5.0
9.8
2.6
4.70
803
6.9
38.2
2
720
160
183
5.74
4.08
989
4.5
9.7
2.4
4.45
759
6.2
38.4
1
643
160
172
5.20
3.68
895
3.7
9.5
2.2
4.06
693
5.3
38.8
η
se, max
5
1360
135
274
9.63
7.04
1659
11.5
11.2
3.8
7.21
1232
15.1
35.8
4
1305
135
250
9.34
6.81
1607
10.9
11.0
3.7
7.00
1196
14.3
36.0
3
1222
135
231
8.87
6.44
1527
9.9
10.9
3.5
6.67
1139
13.1
36.3
2
1152
135
216
8.47
6.13
1458
9.1
10.7
3.4
6.38
1090
12.1
36.5
1
1059
135
205
7.92
5.71
1364
8.1
10.5
3.2
6.00
1024
10.8
36.9
V
L, max
5
2826
25
422
16.09
12.50
2770
29.4
13.5
5.2
11.92
2035
37.8
32.6
4
2689
23
398
15.59
12.04
2683
27.7
13.3
5.1
11.54
1971
35.7
32.8
3
2529
20
375
14.97
11.50
2577
25.8
13.1
5.0
11.09
1893
33.2
33.1
2
2336
17
361
14.20
10.83
2445
23.4
12.8
4.9
10.52
1796
30.1
33.4
1
2099
14
310
13.20
9.97
2273
20.5
12.5
4.7
9.79
1671
26.4
33.9
Heating (2 pipe rows)
: t
W1
= 45 °C, t
W2
= 40 °C, t
R
= 20 °C
Cooling (4 pipe rows)
: t
W1
= 7 °C, t
W2
= 12 °C, t
R
= 27 °C, HR = 47 %
Available static pressure values with clean filter.