NBS – Fan coil unit
TECHNICAL DOCUMENTATION
Accessories
LWZ
-AT01
Construction subject to change.
No return possible.
Version: 06.05.21 | Page 18
ACCESSORIES
NOTE
All accessories are supplied loose for mounting on site
outside the NBS.
ACTUATORS
Code
Model
Actuator signal Operating voltage
AT01
SAST127474
ON/OFF
NC
230 V AC
50/60 Hz
AT02
SAST127475
ON/OFF
NC
24 V AC/DC
50/60 Hz
AT03 SAPV127957
DC 0…10 V
NC
24 V AC
50/60 Hz
AT04 SAPV128561
DC 0…10 V
NC
24 V DC
AM01 SMPV132351
DC 0…10 V
24 V AC/DC
50/60 Hz
AM02 SMPO132353
DC 0…10 V
24 V AC/DC
50/60 Hz
AT = thermal | AM = motorised
PRESSURE INDEPENDENT CONTROL VALVES
1.- The volumetric flow [l/h] can be found in the technical
documentation or in the SCHAKO design program.
2.- Selection of the optimum valve. The valve must be
operated at approx. 80% of its V
Wmax
.
NOTE
The valve and the actuator can be adjusted on site without
tools.
NOTE
The unit has no external condensate pan. The valves
must be thermally insulated on site.
Code
Model
DN
H
100
(mm)
Connection
(Inch)
V
W min. - max
.
(l/h)
VC01
VPP46.10L0.2 10
2.5
G ½
30 - 200
VC02
VPP46.10L0.4 10
4.5
G ½
65 - 333
5.0
65 - 370
VC03
VPP46.15L0.2 15
2.5
G ¾
30 - 200
VC04
VPP46.15L0.6 15
2.5
G ¾
100 - 575
VC05
VPP46.20F1.4 20
4.5
G 1
200 - 1190
5.0
220 - 1330
VC06
VPP46.25F1.8 25
4.5
G 1 ¼
238 - 1530
5.0
260 - 1670
5.5
280 - 1800
VC07
VPP46.32F4.0 32
4.5
G 1 ½
468 - 3400
5.0
510 - 3700
5.5
550 - 4001
VC08 VPP46.10L0.2Q 10
2.5
G ½
30 - 200
VC09 VPP46.10L0.4Q 10
4.5
G ½
65 - 333
2.5
65 - 370
VC10 VPP46.15L0.2Q 15
2.5
G ¾
30 - 200
VC11 VPP46.15L0.6Q 15
2.5
G ¾
100 - 575
VC12 VPP46.20F1.4Q 20
4.5
G 1
200 - 1190
5.0
220 - 1330
VC13 VPP46.25F1.8Q 25
4.5
G 1 ¼
238 - 1530
5.0
260 - 1670
5.5
280 - 1800
VC14
VPP46.32F4Q 32
4.5
G 1 ½
468 - 3400
5.0
510 - 3700
5.5
550 - 4001
VC15
VPI46.15L0.2
15
2.5
Rp ½
30 - 200
VC16
VPI46.15L0.6
15
2.5
Rp ½
100 - 575
VC17
VPI46.20F1.4
20
4.5
Rp ¾
200 - 1190
5.0
220 - 1130
VC18
VPI46.25F1.8
25
4.5
Rp 1
238 - 1530
5.0
260 - 1670
5.5
280 - 1800
VC19
VPI46.32F4.0
32
4.5
Rp 1 ¼
468 - 3400
5.5
510 - 3700
5.0
550 - 4001
VC20 VPI46.15L0.2Q 15
2.5
Rp ½
30 - 200
VC21 VPI46.15L0.6Q 15
2.5
Rp ½
100 - 575
VC22 VPI46.20F1.4Q 20
4.5
Rp ¾
200 - 1190
5.0
220 - 1330
VC23 VPI46.25F1.8Q 25
4.5
Rp 1
238 - 1530
5.0
260 - 1670
5.5
280 - 1800
VC24 VPI46.32F4.0Q 32
4.5
Rp 1 ¼
468 - 3400
5.0
510 - 3700
5.5
550 - 4001
Maximum allowed differential pressure = 600 kPa
Rp = female thread | G = male thread
DN = nominal width | H
100
= nominal stroke | | V
W
= water volumetric
flow |Δp = allowed differential pressure for the valve