Installation, Mounting and Maintenance DISA-360
Z11/35 - 8
Construction subject to change.
No return possible!
Version:
Checks
Prior to commissioning, the following items must be checked or
guaranteed:
During commissioning itself, the following items must be guar-
anteed:
Maintenance
For reasons of safety, the power supply and hydraulic circuit
must be disconnected prior to any maintenance activity. If the
unit was operated in heating mode, you have to wait until the
register has cooled down.
Folding down of the secondary air grille
The entire DISA-360 is equipped with a series of safety locks,
which allow the grille to be folded down via a rotating mecha-
nism on one of the profiles for safe execution of maintenance.
The secondary air grille is folded down as described below:
Clean them with an industrial vacuum cleaner or steam cleaner
or by spraying it with a non-aggressive cleaner.
- Hydraulic connections were tightened properly and exhib-
it no leaks.
- Connecting and fastening elements have been sufficiently
tightened.
- Adequate access for carrying out the maintenance activi-
ties has been provided.
- Use the on-site ventilation devices to ensure that no air re-
mains in the register and the water circuit.
- The connecting and fastening elements have been suffi-
ciently tightened.
- In heating mode, the temperature of the discharged sup-
ply air is not above 40°C.
- Open the safety locks.
- Fold the grille down.
- This makes the grille and the registers freely accessible
for cleaning purposes.
- After having carried out the maintenance work, the grille is
placed again in its original work position. Make sure that the
locks are engaged.
After these items have been taken care of,
the correct fastening of the device must be
When performing maintenance activities, it is rec-
ommended wearing personal protective equip-
ment, in order to avoid cuts and other injuries
produced by sharp and pointed parts.
1
2