Installation, Mounting and Maintenance DISA-360
Z11/35 - 6
Construction subject to change.
No return possible!
Version:
Installation
The ceiling induction diffuser type DISA-360 is particularly suit-
able for horizontal installation in low false ceiling heights. The
devices must not be installed in places with extreme moisture
(e.g. laundries or swimming pools), aggressive media, with
high dust formation, outdoors or in places subject to explosion
hazards. For correct installation, the following instructions must
be followed:
Mounting
The induction diffusers are mounted to load-bearing ceiling
constructions using threaded bars, nuts and M6 or M8 washers.
Use only fastening material approved by the building superviso-
ry authorities.
During mounting the end of the register pipes must be sealed to
protect them from dust and dirt.
Hydraulic connections
The connection of the hydraulic connections can be done by sol-
dering, pressing (in connection with supporting sleeves) or by
means of flexible hoses resistant to oxygen diffusion and push-
fit systems. The use of flexible hoses is subject to the manufac-
turer's specification.
When making the hydraulic con-
nections, you have to use suitable
tools to avoid excessive tighten-
ing or twisting of the register
connections.
- Make sure that places that are intended as openings for air
admission and air discharge are free of pipes, electric ca-
bles, crossbeams, stands, etc.
- Install the unit at a site that has good air quality.
- Make sure that wall and ceiling correspond to the weight
of the device and also allow correct mounting of the fas-
tening elements in the ceiling.
- The installation site must have sufficient space and the
necessary resources for carrying out mounting and main-
tenance activities of all device components. Make sure that
the valves are easily accessible.
- The hydraulic pipes should be attached above the device.
- If the hydraulic pipework is lower than the input of the de-
vice, a ventilation opening must be provided on site.
BxLG
592
x
592
592
x
1192
597
x
597
597
x
1197
617
x
617
617
x
1242
622
x
622
622
x
1247
E -H
625
630
625
630
-V
550
555
550
555
F
409 1009 414 1014 409 1034 414 1039
L
LG
55
55
E
F
Water capacity
(litres)
NL
Heating
Cooling
600
0,35
0,88
1,17
1200
0,79
2,1
2,8
For the installation of the device, use adequate
tools, devices and materials and observe the safety
regulations and other current regulations.
SCHAKO cannot be held liable for damage result-
ing from faulty installation or the use of unsuitable
fastening devices.
159
103
103
159
66
122
Heating
Cooling
DISA-360-H (2-pipe)
DISA-3604-pipe (-HT)