![Schako BSK-EN Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/schako/bsk-en/bsk-en_installation-mounting-and-operating-instructions_1210030016.webp)
BSK-EN fire damper
INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS
Tender text
Construction subject to change
No return possible
Version: 2018-11-14 | Page 16
Extension part type VT,
for installation with large wall/cei-
ling thicknesses; to maintain the minimum distance a
min
= 50
mm from the open damper leaf when mounting the finishing
protective grating type ASG, flexible connecting piece type
FS or pipe connecting piece type RS. Extension part made of
galvanised profiled sheet steel fitted with connecting flan-
ges, L=180 mm (damper height 200 to 750 mm), L=210 mm
(damper height 800 mm).
Product: SCHAKO
type VT
Dimensions:
Width (B): .................... mm
Height (H): .................... mm
•
Extra charge for anticorrosive paint - inside/outside -
DD coating (two-component paint, PU-based - RAL
7035 / light grey)
•
Extra charge for powder coating, inside/outside (RAL
9010 / pure white)
Flexible connecting piece type FS
consisting of profiled
connection flanges (galvanised sheet steel) with elastic in-
termediate piece made of polyester fabric PVC-coated on
both sides, standard flammable according to EN 13501-1,
with welded lip seals (sealing degree C according to EN
13180 / EN 1507; temperature-resistant from -20° to 80°C).
Flexible part of the connecting piece (polyester fabric) must
have a length l
min
of 100 mm when mounted, this gives an
installation dimension of approx. L=160 mm.
The required equipotential bonding must be implemented
on-site according to the VDE or local regulations. The fire
dampers must not be subject to mechanical stress under any
circumstances.
Product: SCHAKO
type FS
Dimensions:
Width (B): .................... mm
Height (H): .................... mm
Finishing protective grating ASG,
for mounting with ventila-
tion duct connection only one side, galvanised sheet steel,
mesh size ≤ 20 mm, minimum distance a
min
= 50 mm from the
open damper blade must be taken into account, if necessary,
use extension part type VT.
Product: SCHAKO
type ASG
Dimensions:
Width (B): .................... mm
Height (H): ..................... mm
•
Extra charge for anticorrosive paint - inside/outside -
DD coating (two-component paint, PU-based - RAL
7035 / light grey)
•
Extra charge for powder coating (RAL 9010 / pure
white)
Pipe connecting pieces type RS
, for connecting round ventila-
tion ducts to BSK-EN, consisting of joining plate with bores and
pipe connecting piece, galvanised sheet steel.
Product: SCHAKO
type RS
Dimensions (W;H according to damper size):
Width (B): .................... mm
Height (H): ......................mm
Duct connecting piece ø (øD):.......mm
•
Extra charge for anticorrosive paint - inside/outside -
DD coating (two-component paint, PU-based - RAL
7035 / light grey)
•
Extra charge for powder coating, inside/outside (RAL
9010 / pure white)