BSK-EN fire damper 

 

INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS 

 

Accessories  

 

Construction subject to change 

 

No return possible 

Version: 2018-11-14 | Page 13 

EXTENSION PART TYPE VT 

 

 

Figure 13: Extension part type VT 

 

 

Extension  part  made  of  profiled  sheet  steel  fitted  with 
connecting flanges. 

 

Intended use: for large wall/ceiling thicknesses, in order to 
maintain a minimum distance a

min

 = 50 mm from the open 

damper blade when fitting protective finishing grating type 
ASG, flexible connecting pieces type FS or connecting pipes 
type RS 

 

[mm] 

[mm] 

The L dimension

 depen

d

s on th

e

 h

eight.

 

200 

180 

250 

300 

350 

400 

450 

500 

550 

600 

650 

700 

750 

800 

210 

 

Table 9: Length of the extension part type VT depending on the fire 
damper height 

 

FLEXIBLE CONNECTING PIECE TYPE FS 

 

Figure 14: Flexible connecting piece type FS 

 

 

Flexible connecting piece consisting of profiled connection 
flanges  (galvanised  sheet steel)  with  elastic  intermediate 
piece made of polyester fabric PVC-coated on both sides, 
standard flammable according to EN 13501-1, with welded 
lip  seals  (sealing  degree  C  according  to  EN  13180  /  EN 
1507;  temperature-resistant  from  -20°  to  80°C).  Flexible 
part of the connecting piece (polyester fabric) must have a 
length l

min

 of 100 mm when mounted, this gives an instal-

lation dimension of approx. L=160 mm. 

 

The  required  equipotential  bonding  must  be  carried  out 
on-site according to the VDE or local regulations.  The fire 
dampers must not be subject to mechanical stress under 
any circumstances. 

 

Flexible ventilation ducts made of steel or aluminium can 
be used instead of the flexible connection pieces. 

 

Flexible spigot must be installed in the scrapped state. This 
may reduce the free cross section. An extension piece may 
be necessary. 

 

For H ≥ 400, observe table 2 page 4. 

 

DUCT CONNECTION SPIGOT TYPE RS 

 

 

 

W x H 

[mm] 

øD 

[mm] 

200x200 

198 

250x250 

248 

400x400 

398 

450x450 

448 

500x500 

498 

600x600 

558 

650x650 

628 

750x750 

708 

800x800 

798 

 

Figure 15: Pipe connecting piece type RS 

 

 

Pipe connecting pieces with joining plate, galvanised sheet 
steel. 

 

Intended  use:  connection/transition  fire  damper  to  round 
ducts. 

 

Other dimensions on request. 

 

For H ≥ 400, observe table 2 page 4. 

Equipotential bonding 

(on site) 

Содержание BSK-EN

Страница 1: ...dimensions 3 Mounting information 5 Installation information 6 Technical data 7 Accessories 9 Legend 14 Specification text 15 Identification label 17 Maintenance or functional test 18 Certificate of...

Страница 2: ...be connected both on non combustible and com bustible ventilation ducts MODELS Housing made of galvanised sheet steel cold and hot leakage requirements according to EN 1366 2 are met u sing circumfer...

Страница 3: ...50 650 700 700 750 750 800 800 900 1000 1100 1200 1300 1400 1500 Table 1 Available sizes Housing length L 500 mm All width and height dimensions can be combined Release device always on H side On requ...

Страница 4: ...cting piece RS Pipe connecting piece a 50 mm Minimum distance between the front edge of the open damper leaf and the fi nishing protective grating ASG flexible connecting piece FS or pipe connecting p...

Страница 5: ...otection mortar of the cor responding grade The minimum gap size smin is 50 mm If the fire damper is installed during the construction of the ceiling the gaps s can be omitted The mortar bed depth has...

Страница 6: ...hey must be created in the direct vicinity in the connected ventilation ducts Inspection o penings are not available therefore they must be created in the direct vicinity in the connected ventilation...

Страница 7: ...LWA dB A KF1 LWA2 dB A LWA1 dB A x KF2 LWA Abst1 dB A LWA1 dB A KF3 LWA1 Abst2 dB A LWA2 dB A KF3 p1 p x KF4 p2 p1 x KF5 200 3 1 05 7 2 15 1 66 250 3 1 07 7 1 8 1 69 300 2 1 09 7 1 55 1 72 350 2 1 10...

Страница 8: ...3 40 1 41 8 45 4 49 0 52 5 56 1 59 6 63 2 66 7 Table 4 Weight table kg FREE CROSS SECTION Free cross section m2 Width mm 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 140...

Страница 9: ...VT 1 Pipe connecting piece type RS 1 1 Standard model galvanised sheet steel powder coated RAL 9010 pure white and DD coating RAL 7035 light grey possible LIMIT SWITCH TYPE ES Electric limit switch fo...

Страница 10: ...sition is possible in the de energised state It is unlocked manually On site function control is possible by means of the control key of BAT or BAE72B S Spare parts Temperature fuse for temperature in...

Страница 11: ...dimensions BSK EN with B10 B11 approx 102 mm BSK EN with B20 B21 approx 106 mm BSK EN with B30 B31 approx 120 mm Figure 12 Damper dimensions 200 225 250 275 300 325 350 375 400 450 500 550 600 650 700...

Страница 12: ...IEC EN II protective insulation Degree of protection IEC EN IP54 Ambient temperature Normal operation 30 55 C 30 50 C Storage temperature 40 55 C 40 50 C Ambient humidity 95 r H non condensing Table...

Страница 13: ...ard flammable according to EN 13501 1 with welded lip seals sealing degree C according to EN 13180 EN 1507 temperature resistant from 20 to 80 C Flexible part of the connecting piece polyester fabric...

Страница 14: ...he flow generated noise adjusted for diffe rent values of B mm in the model with finishing protective grating ASG KF2 dB A A weighted sound power level of the flow generated noise adjusted for diffe r...

Страница 15: ...eft Unless specified otherwise in the order details the mechani cal model Right and fusible link with trigger temperature 72 C is supplied Alternative models or accessories at an extra charge select a...

Страница 16: ...80 C Flexible part of the connecting piece polyester fabric must have a length lmin of 100 mm when mounted this gives an installation dimension of approx L 160 mm The required equipotential bonding mu...

Страница 17: ...to change No return possible Version 2018 11 14 Page 17 IDENTIFICATION LABEL 1035 13 SCHAKO Iberia S L Pol Ind R o G llego Calle B nave 3 E 50840 San Mateo de G llego Zaragoza 14 ESPA A 01 01 DoP BSK...

Страница 18: ...h into the swivelling range of the damper leaf and hand lever There is a risk of injury The fire damper must close automatically 1 1 3 Test of the snap in locking device Pull the disc pos 1 at the han...

Страница 19: ...r Press switch pos 1 on the thermoelectric trigger device pos 2 thus the spring return actuator is disconnected from the power supply pos 3 alternatively interrupt on site power supply Fire damper mus...

Страница 20: ...______________ The following function steps have been carried out according to the documents Installation mounting and operating instruc tions before commissioning Next functional check in ___________...

Страница 21: ...4 Page 21 Functional test protocol for fire dampers Cons no ____________________ Defects found during the test on _____________________ Sluggishness due to soiling Any remaining mortar must be removed...

Отзывы: