Installation
Requirements
This insert can be installed in most solid fuel burning fire-
places of either masonry construction or a prefabricated
factory built fireplace.
Prior to any installation, the existing chimney exhaust
flue must be thoroughly cleaned and completely in-
spected by a qualified chimney sweep or fireplace service
person.
Do not install this insert into a chimney that is dam-
aged. Any repairs must be made prior to installing the
insert. If you are unsure of the condition of your fireplace
and chimney, contact a professional fireplace technician
or your local authorized Scan dealer for professional as-
sistance.
Figure 2. Firebox dimensions.
Leg Leveling Bracket Note:
Two right and left brackets with mounting
hardware are included in the Miscellaneous Kit.
Installation of the brackets allows the insert to
be raised up to 2 1/2” off of the hearth.
Also note that use of the leveling brackets
will affect required minimum clearance to
combustible top trim and mantle construction.
See the figures and tables on pages 8 and 9.
DO NOT REMOVE BRICKS OR MORTAR FROM THE
FIREPLACE OR CHIMNEY STRUCTURE.
However, masonry
or steel may be removed from the smoke shelf and ad-
jacent damper frame area to accommodate installation
of a chimney liner, provided that their removal will not
weaken the structure of the fireplace or chimney, and will
not reduce protection for combustible materials.
If the fireplace has been modified to accommodate
installation,
use anchors or masonry nails to attach the
metal Fireplace Conversion Notice Plate to the back wall
of the masonry fireplace firebox where it will be readily
seen should the insert be removed.
THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE OF
ANY KIND. All venting components must be installed in
accordance with the terms of their listing and manu-
facturer’s instructions. Refer to the pipe manufacturer’s
instructions for proper pipe clearances.