139234_Rev_A    9.17 .10

Figure 10.  Duct collar locations.

Exhaust 

Collar

Air Inlet 

Collar

Dual 3” Listed Liners

Prefabricated Fireplace Vent Procedure

1.  Measure height of the chimney to fireplace open-

ing.  Determine if both the intake and exhaust 

will be extended to the top of the chimney.

2.  Cut the appropriate lengths of flex for both the 

intake and exhaust.

3.  

If the intake flex will be attached to the chimney 

termination kit:

 Attach the appropriate ends of 

the flex to the chimney termination kit. 

  CAUTION: AVOID CROSS-VENTING THE FLEX PIPE.

Label the end of the exhaust pipe.

4.  Drop the liners down the chimney from the top 

and rest the termination kit atop the chimney.

5.  Seal the chimney termination kit to the top of the 

chimney pipe with high temperature sealant.

6.  Secure the appropriate DIRECT VENT CAP to the 

termination kit.

7.  Inside the fireplace, fully extend the flex and cut 

off the excess flex so that the liners hang approxi-

mately 15” from the floor of the fireplace.

8. 

 If the intake flex is NOT attached to the chimney 

termination kit:  See NOTICE on page 12.

  A. It is necessary to install a minimum 6 foot 

length of flex pipe into the flue for the intake air. 

  B.  A METAL damper block off plate must be 

constructed and installed in the damper area to 

completely seal off the flue from the room.  Cut 

holes for both the intake and exhaust liners in the 

block off plate.

  C.  A direct vent cap is still required to allow fresh 

air into the chimney flue and ultimately into the 

intake flex and insert. 

D.  Attach the Fireplace Conversion Notice to the 

back of the fireplace if appropriate.

9.  Surround panels must not block or seal any venti-

lation openings on the prefabricated fireplace.

Vent Connection

Wear Safety Gloves!

1.  Push the insert partially into the fireplace cavity, 

leaving access to the duct collars.

2.   Identify the end of the Exhaust duct and secure it 

to the collar on the insert using a clamp.

3.  Secure the other duct to the collar labeled AIR 

INTAKE.

Final Positioning

1.   Blower Power Cord: 

Extend the blower power cord out forward of the 

fireplace, routing it to the nearest power source.  

Measured from the fireplace center line, It can extend 

up to 5 1/2 feet to the right, and up to 3 1/2 feet to the 

left.

  A 10 foot long extension cord is available from your 

Scan dealer, PN 223253.

2.  Level and Plumb the Cabinet:

With the fireplace cabinet in its final position, con-

firm that it is level and plumb.  

       Adjust the leg levelers at each corner as appropri-

ate to fine-tune the level up to 1/2”. If a greater height 

increase is required, the brackets can be lowered in 

1/2” increments to raise the cabinet up to 2 1/2”.

WARNING: FAILURE TO POSITION THE PARTS IN 

ACCORDANCE WITH THIS DIAGRAM OR FAILURE TO 

USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS 

APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR 

PERSONAL INJURY.

Содержание 45i

Страница 1: ...l Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trou vant dans le b timent o vous trouvez Appelez imm diatement votre fournis seur de gaz depuis un voisin Suivez les instructions...

Страница 2: ...ucts be installed and serviced by professionals who are certified in the U S by the National Fireplace Institute NFI as NFI Gas Specialists THIS PRODUCT MUST BE INSTALLED BY A LICENSED MASTER OR JOURN...

Страница 3: ...the glass out of the way 5 The Starfire Glass Embers or Tumbled Stone burner media is packaged separately from the insert firebox Figure 1 Pull each Trunk Latch down to disengage it from the Glass Fr...

Страница 4: ...an 45i gas fireplace insert has been tested and listed as a direct vent gas fireplace heater and listed to ANSI Z21 88 2009 CSA 2 33 2009 CAN CGA 2 17 M91 and CSA P 4 01 2 for Canada Starfire Glass Em...

Страница 5: ...ve been established in CAN CGA B149 Fuel Installation Code Installer l appareil selon les codes ou reglements locaux ou en l absence de tels reglements selon les Codes d installation CAN CGA B149 5 Do...

Страница 6: ...ace Never burn any solid materials wood cardboard paper coal etc in this gas fireplace Use with natural gas or propane fuel ONLY Any safety screen glass or guard removed for servicing the appliance mu...

Страница 7: ...tallation of the brackets allows the insert to be raised up to 2 1 2 off of the hearth Also note that use of the leveling brackets will affect required minimum clearance to combustible top trim and ma...

Страница 8: ...18 forward of the firebox glass panel Raised Hearth A raised hearth that is at least 6 high requires a non combustible hearth that extends a minimum 12 from the fireplace glass and and is a minimum o...

Страница 9: ...ment This appliance requires 120 V AC power to operate the blower accent lamps and electronic ignition Four AA batteries provide back up power in case of a power outage Leg Leveler Bolts and Brackets...

Страница 10: ...3 M99 TEST METHODS AND RESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Vent Guidelines All vent compo...

Страница 11: ...into the chimney flue and ultimately into the intake duct to the insert 9 Compress the ducts so that they are hanging above the height of the fireplace opening and are out of the way 10 Position the i...

Страница 12: ...ESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Figure 9 Venting through prefabricated fireplace chimn...

Страница 13: ...ut holes for both the intake and exhaust liners in the block off plate C A direct vent cap is still required to allow fresh air into the chimney flue and ultimately into the intake flex and insert D A...

Страница 14: ...13 85 WC NECESSARY MANIFOLD PRESSURES inches water column MIN MAX NATURAL GAS 1 6 WC 3 5 WC PROPANE 5 3 WC 11 0 WC ALWAYS TEST PRESSURE WITH THE VALVE REGULATOR ADJUSTED TO THE HIGHEST SETTING Figure...

Страница 15: ...ilot rectification and or frequent burner outages Little variation in flame picture between HI and LO regulator settings Insufficient gas to support more than one ap pliance causing nuisance outages o...

Страница 16: ...BLIS DANS LES IN STRUCTIONS DE PROPRIETAIRE PROVISIONNEES AVEC L EQUIPEMENT Conversion Kit LP 157249 NG 157250 Tools required 1 2 13 mm open end wrench or deep well socket Torx T20 driver 1 4 nut driv...

Страница 17: ...ocated it should not be able to move to the right or left 10 Replace the variable regulator on the gas control valve Using a Torx T 20 screwdriver remove the two screws from the regulator tower on the...

Страница 18: ...aller and applied to the appli ance at the time of the conversion See fig 19 Derating procedure 1 Turn off gas supply to the appliance and disconnect from electrical power source 2 Remove the Glass Fr...

Страница 19: ...ening the air shutter will generate a flame that is blue and transparent or an anemic flame This flame is generally more efficient but not very attractive We recommend the following settings for the S...

Страница 20: ...shutter See figs 14 and 15 pages 16 17 4 Use a 10 mm socket to remove the left and right burner bracket nuts Remove the Burner Bracket from the firebox See fig 23 5 Bend the two upper rear tabs down...

Страница 21: ...ure 26 Install Glass Embers Tumbled Stones Kit 157245 NOTE Install the optional Reflective Glass Panels before installing the stones Spread the stones evenly around the burner media tray CAUTION Take...

Страница 22: ...Figure 28 At the thermostat the two wires should be connected to the two connection screws on the thermostat base plate according to the manufacturer s instructions For the thermostat to function the...

Страница 23: ...e Backing Plate or Trimmable Backing Plate See fig 31 Starting at the small precut slot use a straight edge to draw a guideline across the leg Use a disk grinder to cut off the excess material and fil...

Страница 24: ...there is no call for heat Ideal for use with thermostatic or remote control this feature ignites the pilot flame only when there is a call for heat A battery back up permits continued use in the event...

Страница 25: ...not lifting or float ing The flame should be blue in color around the pilot hood with traces of yellow toward the outer edges It is important that the pilot flame engulf the top 1 8 of the flame recti...

Страница 26: ...s and particulate accumulation may appear on the inside surface to the glass Use a dampened soft cloth to clean the glass and polish with a dry soft towel Specially formulated ceramic glass cleaner ma...

Страница 27: ...214 Screw 8 X 1 4 Taptite SLHWH SZPL 21 223980 ProflameValve Manual Hi Lo NG 22 223215 Adaptor Straight Brass 3 8 NTP x 3 8 Dia Flare 23 129707 Flex tube w connectors 3 8 O D x 24 24 222280 Gasket Dro...

Страница 28: ...Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk Oxide 2 222799 Blower Bracket 3 222072 Blower TransFlow 12 Cage 120 CFM No Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk...

Страница 29: ...rs Simpson Dura Vent Inc P O Box 1510 Vacaville CA 95696 1510 800 835 4429 Selkirk Corporation 1301 W President George Bush Hwy Suite 330 Richardson TX 75080 1139 800 992 8368 American Metal Products...

Страница 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Страница 31: ...ouch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone If your gas supplier cannot be reached call the fire department 1 Set the...

Страница 32: ...ion it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specification color or ty...

Отзывы: