Wall Thermostat

Use only a 750 millivolt DC two-wire circuit thermostat. 

The thermostat should be placed in the same room as 

the heater, typically 5’ off the floor.  Avoid drafty areas or 

any area that may affect the accuracy of the thermostat.

The thermostat should be connected to the burner 

switch terminal block using a minimum 16 gauge wire 

having a maximum length of 35 feet of wire.

Remove the Burner  Controls face plate with removal 

of the two #8 hex head screws. 

Connect the two thermostat wire leads to the two 

open terminals on the terminal block located on the 

back of the face plate between the two switches. Do not 

overtighten the connections. 

 S

ee Figure 28.

At the thermostat, the two wires should be 

connected to the two connection screws on the 

thermostat base plate according to the manufacturer’s 

instructions.

For the thermostat to function, the ON/OFF/T-STAT 

switch must be in the T-STAT position. The thermostat 

will then control the burner function with the Pilot 

switched to either IPI or CPI modes.

Figure 28.  Wall thermostat / Remote Control connections.

Remote Control #129706

The optional    Remote Control can be used with the 

Scan 45i, however, the receiver must be installed 

outside

 

of the unit. 
If there is no room for it within the fireplace, consider 

installing the receiver in a nearby wall.  

Use 200°C, 18 ga. 

wire for extension, if needed. Keep all wiring from direct 

contact with the insert firebox bottom.

Remove the burner control face plate and connect the 

remote receiver leads to the two open terminals shown 

in fig. 28. 

Содержание 45i

Страница 1: ...l Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trou vant dans le b timent o vous trouvez Appelez imm diatement votre fournis seur de gaz depuis un voisin Suivez les instructions...

Страница 2: ...ucts be installed and serviced by professionals who are certified in the U S by the National Fireplace Institute NFI as NFI Gas Specialists THIS PRODUCT MUST BE INSTALLED BY A LICENSED MASTER OR JOURN...

Страница 3: ...the glass out of the way 5 The Starfire Glass Embers or Tumbled Stone burner media is packaged separately from the insert firebox Figure 1 Pull each Trunk Latch down to disengage it from the Glass Fr...

Страница 4: ...an 45i gas fireplace insert has been tested and listed as a direct vent gas fireplace heater and listed to ANSI Z21 88 2009 CSA 2 33 2009 CAN CGA 2 17 M91 and CSA P 4 01 2 for Canada Starfire Glass Em...

Страница 5: ...ve been established in CAN CGA B149 Fuel Installation Code Installer l appareil selon les codes ou reglements locaux ou en l absence de tels reglements selon les Codes d installation CAN CGA B149 5 Do...

Страница 6: ...ace Never burn any solid materials wood cardboard paper coal etc in this gas fireplace Use with natural gas or propane fuel ONLY Any safety screen glass or guard removed for servicing the appliance mu...

Страница 7: ...tallation of the brackets allows the insert to be raised up to 2 1 2 off of the hearth Also note that use of the leveling brackets will affect required minimum clearance to combustible top trim and ma...

Страница 8: ...18 forward of the firebox glass panel Raised Hearth A raised hearth that is at least 6 high requires a non combustible hearth that extends a minimum 12 from the fireplace glass and and is a minimum o...

Страница 9: ...ment This appliance requires 120 V AC power to operate the blower accent lamps and electronic ignition Four AA batteries provide back up power in case of a power outage Leg Leveler Bolts and Brackets...

Страница 10: ...3 M99 TEST METHODS AND RESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Vent Guidelines All vent compo...

Страница 11: ...into the chimney flue and ultimately into the intake duct to the insert 9 Compress the ducts so that they are hanging above the height of the fireplace opening and are out of the way 10 Position the i...

Страница 12: ...ESULTING ITS WHI PRODUCT CERTIFICATION THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD Figure 9 Venting through prefabricated fireplace chimn...

Страница 13: ...ut holes for both the intake and exhaust liners in the block off plate C A direct vent cap is still required to allow fresh air into the chimney flue and ultimately into the intake flex and insert D A...

Страница 14: ...13 85 WC NECESSARY MANIFOLD PRESSURES inches water column MIN MAX NATURAL GAS 1 6 WC 3 5 WC PROPANE 5 3 WC 11 0 WC ALWAYS TEST PRESSURE WITH THE VALVE REGULATOR ADJUSTED TO THE HIGHEST SETTING Figure...

Страница 15: ...ilot rectification and or frequent burner outages Little variation in flame picture between HI and LO regulator settings Insufficient gas to support more than one ap pliance causing nuisance outages o...

Страница 16: ...BLIS DANS LES IN STRUCTIONS DE PROPRIETAIRE PROVISIONNEES AVEC L EQUIPEMENT Conversion Kit LP 157249 NG 157250 Tools required 1 2 13 mm open end wrench or deep well socket Torx T20 driver 1 4 nut driv...

Страница 17: ...ocated it should not be able to move to the right or left 10 Replace the variable regulator on the gas control valve Using a Torx T 20 screwdriver remove the two screws from the regulator tower on the...

Страница 18: ...aller and applied to the appli ance at the time of the conversion See fig 19 Derating procedure 1 Turn off gas supply to the appliance and disconnect from electrical power source 2 Remove the Glass Fr...

Страница 19: ...ening the air shutter will generate a flame that is blue and transparent or an anemic flame This flame is generally more efficient but not very attractive We recommend the following settings for the S...

Страница 20: ...shutter See figs 14 and 15 pages 16 17 4 Use a 10 mm socket to remove the left and right burner bracket nuts Remove the Burner Bracket from the firebox See fig 23 5 Bend the two upper rear tabs down...

Страница 21: ...ure 26 Install Glass Embers Tumbled Stones Kit 157245 NOTE Install the optional Reflective Glass Panels before installing the stones Spread the stones evenly around the burner media tray CAUTION Take...

Страница 22: ...Figure 28 At the thermostat the two wires should be connected to the two connection screws on the thermostat base plate according to the manufacturer s instructions For the thermostat to function the...

Страница 23: ...e Backing Plate or Trimmable Backing Plate See fig 31 Starting at the small precut slot use a straight edge to draw a guideline across the leg Use a disk grinder to cut off the excess material and fil...

Страница 24: ...there is no call for heat Ideal for use with thermostatic or remote control this feature ignites the pilot flame only when there is a call for heat A battery back up permits continued use in the event...

Страница 25: ...not lifting or float ing The flame should be blue in color around the pilot hood with traces of yellow toward the outer edges It is important that the pilot flame engulf the top 1 8 of the flame recti...

Страница 26: ...s and particulate accumulation may appear on the inside surface to the glass Use a dampened soft cloth to clean the glass and polish with a dry soft towel Specially formulated ceramic glass cleaner ma...

Страница 27: ...214 Screw 8 X 1 4 Taptite SLHWH SZPL 21 223980 ProflameValve Manual Hi Lo NG 22 223215 Adaptor Straight Brass 3 8 NTP x 3 8 Dia Flare 23 129707 Flex tube w connectors 3 8 O D x 24 24 222280 Gasket Dro...

Страница 28: ...Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk Oxide 2 222799 Blower Bracket 3 222072 Blower TransFlow 12 Cage 120 CFM No Part Number Description 1 117917 Screw HWH SMA 8 x 1 2 SL Blk...

Страница 29: ...rs Simpson Dura Vent Inc P O Box 1510 Vacaville CA 95696 1510 800 835 4429 Selkirk Corporation 1301 W President George Bush Hwy Suite 330 Richardson TX 75080 1139 800 992 8368 American Metal Products...

Страница 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Страница 31: ...ouch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone If your gas supplier cannot be reached call the fire department 1 Set the...

Страница 32: ...ion it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specification color or ty...

Отзывы: