7.0  Installation 

 

Hydrogen gas has only 7% of the density of air, and thus rises. Your hydrogen gas detector 
should be installed at the highest, draft-free location in the battery room, cabinet, or 
compartment where hydrogen gas would accumulate.  
 
Carefully remove the cover by pulling it off the detector.  Attach the detector to the wall, ceiling, 
or optional junction box using the mounting holes at the top and bottom of the detector mounting 
plate. 
 
For hard wiring using conduit, the detector box will fit onto the optional junction box.

 

 
The detector has terminal blocks for connection to a single-phase 120 VAC 50/60 Hz power 
source, OR a +12 VDC Regulated Power Source or a +14-48 VDC power source.  It also has 
two internal alarm relays.  A 1% warning relay that is activated at 1% concentration of hydrogen 
gas and a 2% alarm relay that is energized at 2% concentration of hydrogen gas. The relays 
can be used to switch on a remote exhaust fan and/or to turn on an alarm. 
 
For 120 VAC power, use 18 gage stranded wire minimum (Belden 19348, equivalent or better). 
For relay wires, use stranded wire (Belden 8473, equivalent or better). Maximum wire size for 
connector terminations is 14 AWG stranded copper wire. 
 

Power Requirements:  

 

 Current (A)   

       Power (W) 

 

Voltage 

1 Sensor 

2 Sensors 

1 Sensor 

2 Sensors 

VDC 

12 

0.154 

0.302 

1.848 

3.624 

VDC 

24 

0.090 

0.167 

2.160 

4.008 

VDC 

48 

0.052 

0.090 

2.496 

4.320 

VAC 

120 

0.035 

0.062 

4.200 

7.440 

 
 
The detector's relay dry contacts are rated at 10A/250VAC, sufficient for most 1/3 HP exhaust 
fans. For higher current requirements, add an external relay. 
 
Locate the Sensor installation point within 25 feet of the detector and mount the sensor.  Run 
the supplied cable from the sensor to the detector and connect to the Sensor 1 input labeled on 
the cover. 
 
 

AC Cord

 -

not included  

(

SBS Part# E190399

)

 

Unit shown with 3-prong grounded AC 
Cord (18+ AWG) 
 

Pre-March 2016 Version

Содержание SBS-H2

Страница 1: ...rooms and other areas where hydrogen gas may be present INSTALLATION OPERATING MAINTENANCE INSTRUCTIONS Protects Life Property and Profits 1 800 554 2243 www sbsbattery com TEST sbsbattery com Compli...

Страница 2: ...have to use two or more detectors with 1 or 2 sensors each for increased detection The hydrogen sensor does not provide protection from fires or hydrogen explosions The relay contacts are intended to...

Страница 3: ...ive limit LEL of 4 1 2 0 Benefits In addition to protecting your employees and your property the detector may also reduce the following costs Electricity Heating Air Conditioning Instead of continuous...

Страница 4: ...t supply to the unit Relays 1 Warning Relay 1 Normally Open 1 Normally Closed contact 2 Alarm Relay 1 Normally Open and 1 Normally Closed contact 5 0 Sensor The sensor consists of a ceramic sensing el...

Страница 5: ...gen gas concentration in the air immediately surrounding the sensor Hydrogen gas may accumulate in several areas of the battery compartment or room therefore individual detectors should be installed i...

Страница 6: ...2 alarm relay that is energized at 2 concentration of hydrogen gas The relays can be used to switch on a remote exhaust fan and or to turn on an alarm For 120 VAC power use 18 gage stranded wire minim...

Страница 7: ...le SBS Part H2 100FT CABLE the Sensor jumper must be moved on the sensor input from the off condition to the on condition so it covers both pins 1 Removing the front snap on cover will reveal the inne...

Страница 8: ...er Select between single or multiple sensor set up default jumper settings single sensor Jumper on P9 Only Place a jumper on P8 to disable SENSOR 1 Place a jumper on P9 to disable SENSOR 2 B Signal Ou...

Страница 9: ...ion you would like to use the relay to be related to Use Relay C for the warning condition 1 H2 and relay D for the alarm condition 2 H2 3 Restore the front covering of the alarm box and re secure the...

Страница 10: ...alarm will stop and the 2 relay will de energize When the concentration falls below 1 the 1 relay will de energize and the Yellow LED will turn off 9 0 Electrical Testing after the input power is on...

Страница 11: ...11 SBS H2 Users Manual Rev 1 4 January 6th 2013 Pre March 2016 Version...

Страница 12: ...ther application intended to support or sustain life or for any application in which the failure of the SBS product could create a situation where personal injury or death may occur Should buyer purch...

Отзывы: