6.0  Mounting Location 

 
Hydrogen is colorless and odorless; the lightest of all gases and thus rises. The hydrogen 
sensor, therefore, should be installed at the highest, draft-free location in the battery 
compartment, cabinet, or room where hydrogen gas would accumulate.   
The Alarm Box can be mounted at eye level or wherever is convenient for the user. 
 
The size of the area one sensor will protect depends upon the battery compartment or room. 
The detector measures hydrogen gas concentration in the air immediately surrounding the 
sensor. Hydrogen gas may accumulate in several areas of the battery compartment or room 
therefore; individual detectors should be installed in each of these areas. 
 

Mounting and Power Options:

    

 

Alarm Wiring   

 

 

 

Input Power 

 

 
 
 

Wall Mountable

 

Integrated back mounting plate allows 
user to easily mount directly to any wall 
using qty.2 3/16” screws (not included).  
 

Wiring 

Power and Alarm Wires can be ran 
through the sides of the unit 

Junction Box Mountable  

Mounts to a standard, 4 11/16“ x 4 11/16“  
2-gang junction box (

SBS Part# H2-JB

). 

 
Hardwire 

 

Run AC or DC power and alarm wires through 
back of the unit, into the gang box and out 
through conduit. 

Pre-March 2016 Version

Содержание SBS-H2

Страница 1: ...rooms and other areas where hydrogen gas may be present INSTALLATION OPERATING MAINTENANCE INSTRUCTIONS Protects Life Property and Profits 1 800 554 2243 www sbsbattery com TEST sbsbattery com Compli...

Страница 2: ...have to use two or more detectors with 1 or 2 sensors each for increased detection The hydrogen sensor does not provide protection from fires or hydrogen explosions The relay contacts are intended to...

Страница 3: ...ive limit LEL of 4 1 2 0 Benefits In addition to protecting your employees and your property the detector may also reduce the following costs Electricity Heating Air Conditioning Instead of continuous...

Страница 4: ...t supply to the unit Relays 1 Warning Relay 1 Normally Open 1 Normally Closed contact 2 Alarm Relay 1 Normally Open and 1 Normally Closed contact 5 0 Sensor The sensor consists of a ceramic sensing el...

Страница 5: ...gen gas concentration in the air immediately surrounding the sensor Hydrogen gas may accumulate in several areas of the battery compartment or room therefore individual detectors should be installed i...

Страница 6: ...2 alarm relay that is energized at 2 concentration of hydrogen gas The relays can be used to switch on a remote exhaust fan and or to turn on an alarm For 120 VAC power use 18 gage stranded wire minim...

Страница 7: ...le SBS Part H2 100FT CABLE the Sensor jumper must be moved on the sensor input from the off condition to the on condition so it covers both pins 1 Removing the front snap on cover will reveal the inne...

Страница 8: ...er Select between single or multiple sensor set up default jumper settings single sensor Jumper on P9 Only Place a jumper on P8 to disable SENSOR 1 Place a jumper on P9 to disable SENSOR 2 B Signal Ou...

Страница 9: ...ion you would like to use the relay to be related to Use Relay C for the warning condition 1 H2 and relay D for the alarm condition 2 H2 3 Restore the front covering of the alarm box and re secure the...

Страница 10: ...alarm will stop and the 2 relay will de energize When the concentration falls below 1 the 1 relay will de energize and the Yellow LED will turn off 9 0 Electrical Testing after the input power is on...

Страница 11: ...11 SBS H2 Users Manual Rev 1 4 January 6th 2013 Pre March 2016 Version...

Страница 12: ...ther application intended to support or sustain life or for any application in which the failure of the SBS product could create a situation where personal injury or death may occur Should buyer purch...

Отзывы: