SBS-H2 Users Manual
Rev 1.4
January 6
th
2013
4.0 Specifications
Dimensions:
4.75"L x 5.25"W x 1.4"D (display only)
Wall Mounting:
Two 3/16" screws
Junction Box Mounting:
Requires 4
11/16
” x 4
11/16
” 2-gang junction box (
SBS Part#
H2-JB
)
Power Requirements:
120/220 VAC, 50 / 60 Hz
or
12VDC Isolated or 14 to 48 VDC
*** An earth ground must be supplied to the
GND terminal when using the 12VDC and Isolated (Gnd) inputs for 12 Volt
supply to the unit.
Relays:
1% Warning Relay, 1 Normally Open & 1 Normally Closed contact
2% Alarm Relay, 1 Normally Open and 1 Normally Closed contact
5.0 Sensor
The sensor consists of a ceramic sensing element whose electrical conductivity increases when
hydrogen is adsorbed on its surface. Conductivity of the sensor is proportional to the gas
concentration which is continuously monitored by an electronic circuit. The sensor only monitors
pure hydrogen gas (H2) and will not alarm due to Hydrogen Sulfide (H2S)
– which has an odor
at very low concentrations.
Hydrogen Sensor
25 Ft Cable extension
Pre-March 2016 Version