1.0   Overview 

 

Hydrogen gas detectors act as monitors that provide alarms as well as control functions 
such as controlling exhaust fans, remote alarm and signaling, building management 
interfacing and more for the protection of your facility. 
Batteries on charge emit hydrogen gas after reaching 80% of the recharge point. 
Examples of typical hydrogen emissions per lead-acid battery are: 

 

Battery Size 

Hydrogen Gas 

12 Volt / 500 Amp-Hour 

  3.5 Cubic Feet/hr. 

24 Volt / 720 Amp-Hour 

10.1 Cubic Feet/hr. 

36 Volt / 935 Amp-Hour 

19.8 Cubic Feet/hr. 

48 Volt / 850 Amp-Hour 

23.9 Cubic Feet/hr. 

 

Concentrations of 4.1% to 75% H2 mixed with air can be explosive.  

Sparks or hot surfaces 

can ignite them. A hydrogen gas detector in your battery room will provide a warning and 
facilitate dissipation of hydrogen concentrations before they reach the lower explosive limit 
(LEL) of 4.1%. 

2.0  Benefits 

 

In addition to protecting your employees and your property, the detector may also 
reduce the following costs: 
 

Electricity - Heating - Air Conditioning

 

Instead of continuously running an exhaust fan to prevent hydrogen gas accumulation, use the 
detector to activate the fan only if the concentration reaches 1%. 
 

Insurance 

Installation of a detector in areas where batteries are charged may result in a premium 
reduction. 

3.0  How it Works 

 
Should the concentration of hydrogen gas in the air surrounding the sensor reach 1% by 
volume, the "1% Warning" yellow LED will light and the 1% internal relay will energize. Should 
the hydrogen gas concentration reach 2% by volume, the "2% Alarm" red LED will flash and an 
alarm will sound.   
Either relay can be used to activate a remote exhaust fan and/or alarm. 
 
Automatic operation, continuous monitoring, high sensitivity & stability,and solid state reliability.  
The unit is also intrinsically safe using 120/240 VAC 50/60 Hz or 12-48 VDC operating voltages, 
low in cost and easy and versatile to install. 
 

Pre-March 2016 Version

Содержание SBS-H2

Страница 1: ...rooms and other areas where hydrogen gas may be present INSTALLATION OPERATING MAINTENANCE INSTRUCTIONS Protects Life Property and Profits 1 800 554 2243 www sbsbattery com TEST sbsbattery com Compli...

Страница 2: ...have to use two or more detectors with 1 or 2 sensors each for increased detection The hydrogen sensor does not provide protection from fires or hydrogen explosions The relay contacts are intended to...

Страница 3: ...ive limit LEL of 4 1 2 0 Benefits In addition to protecting your employees and your property the detector may also reduce the following costs Electricity Heating Air Conditioning Instead of continuous...

Страница 4: ...t supply to the unit Relays 1 Warning Relay 1 Normally Open 1 Normally Closed contact 2 Alarm Relay 1 Normally Open and 1 Normally Closed contact 5 0 Sensor The sensor consists of a ceramic sensing el...

Страница 5: ...gen gas concentration in the air immediately surrounding the sensor Hydrogen gas may accumulate in several areas of the battery compartment or room therefore individual detectors should be installed i...

Страница 6: ...2 alarm relay that is energized at 2 concentration of hydrogen gas The relays can be used to switch on a remote exhaust fan and or to turn on an alarm For 120 VAC power use 18 gage stranded wire minim...

Страница 7: ...le SBS Part H2 100FT CABLE the Sensor jumper must be moved on the sensor input from the off condition to the on condition so it covers both pins 1 Removing the front snap on cover will reveal the inne...

Страница 8: ...er Select between single or multiple sensor set up default jumper settings single sensor Jumper on P9 Only Place a jumper on P8 to disable SENSOR 1 Place a jumper on P9 to disable SENSOR 2 B Signal Ou...

Страница 9: ...ion you would like to use the relay to be related to Use Relay C for the warning condition 1 H2 and relay D for the alarm condition 2 H2 3 Restore the front covering of the alarm box and re secure the...

Страница 10: ...alarm will stop and the 2 relay will de energize When the concentration falls below 1 the 1 relay will de energize and the Yellow LED will turn off 9 0 Electrical Testing after the input power is on...

Страница 11: ...11 SBS H2 Users Manual Rev 1 4 January 6th 2013 Pre March 2016 Version...

Страница 12: ...ther application intended to support or sustain life or for any application in which the failure of the SBS product could create a situation where personal injury or death may occur Should buyer purch...

Отзывы: