Saia-Burgess Controls AG
PCD7.D443WTxRx | Document 27-644 | Version ENG04 | 2017-10-30
16
2
Technical data for the two panel types
Because of the programmable logic controller in the programmable panels, the hardware of the
PCD7.D443WTPR and PCD7.D443WT5R Micro Browser Panels differs in certain respects. These
differences are described in the following sections.
Status display, sensors and actions
PCD7.D443WTPRx
PCD7.D443WT5Rx
Reset button
In run:
Button is pressed for longer than
45 sec during operation.
Not available (x)
Program restore will be triggered.
When starting up:
Button is pressed for longer than
45 sec before the power supply
(24V DC) is connected.
Not available (x)
Program restore will be triggered.
When starting up:
Button is pressed for longer than
90 sec before the power supply
(24V DC) is connected. Device re-
set to default factory settings
Device reset to default factory set-
tings, the local INTFLASH and
PLC_SYS file systems will be for-
matted.
Device reset to default factory set-
tings, the local INTFLASH and
PLC_SYS file systems will be for-
matted. User program will be de-
leted.
LED
Important:
Hardware version "< B". Supports the colour green only
Hardware version ">= B". Supports the colours red, green and orange
Status display
See also Chapter 3.2 / 7.6
During the boot process, the LED shows the operating status of the
panel. The LED will go out once the LCD has started successfully.
Temperature sensor
Ac/- 1°C
Temperature range:
Note installation location "1.5.1"
Sensor must be calibrated
See also Chapter 7.6
Yes
0°C to 40°C
Hardware version >= B
FW version >= 1.28.04
Yes
0°C to 40°C
Hardware version >= B
FW version >= 1.28.04