Saia-Burgess Controls AG
PCD7.D443WTxRx | Document 27-644 | Version ENG04 | 2017-10-30
46
7.5.5 uBT_BackLight container diagram
7.5.6 Additional uBTerminal containers for "Save logs to File" function
Name of the contai-
ner
Default
Meaning
Access
uBT_TrendPath
Dynamically linked file path
Only readable
uBT_TrendDevice
INFLASH:
Energy saving facility
Only readable
uBT_TrendDir
WEBPAGES/
Subdirectory for saving all trends.
Read
uBT_TrendSDFlash
0
0: INTFLASH (SVGA)
Read/write
uBT_TrendPrefix
TR
File name prefix, max. 5 characters
Read/write
uBT_TrendSave
File last saved.
Only readable
uBT_TrendLoad
File currently loaded.
Read/write
uBT_TrendSelect
Last file in the di-
rector
File currently selected. Value will be set when sav-
ing a trend ith the sa ed file name
Read/write
uBT_TrendOldest
Changes the
uBT_Trend-
Select container.
Used in the
event of button
actions.
Select oldest file.
Only writable
uBT_TrendNewest
Select newest file.
Only writable
uBT_TrendPrev
Select previous file.
Only writable
uBT_TrendNext
Select next file.
Only writable
uBT_TrendDelAll
Use in the event
of button actions.
Delete all files in the directory.
Only writable
uBT_TrendDelSel
Delete file currently selected.
Only writable
uBT_TrendDelLast
Delete last file saved.
Only writable
uBT_TrendDelOld
Delete all files that are older than the selected file.
Only writable
Example: The online minimal S2F macro for the MB Panel
"MB_OnlineTrendMinimal_5_13_01.esm"