Saia-Burgess Controls AG
PCD7.D443WTxRx | Document 27-644 | Version ENG04 | 2017-10-30
39
The temperature value can be passed on to the controller by Web Editor 8 for the user ap-
plication with the following steps:
1) First of all, a background page for all pages in your project should be set up for the
project. This page is permanently worked through by the panel.
Important:
The MSGBox page and "entry pages" like the keyboard stop communication between
the panel and controller.
2) A result box must be placed on the background page which is active in all views.
3) An action when updating must be set up in this result box.
4) The temperature value which is available in the internal variable (INT)
uBT_Watch,Temperature,value
must be written to a PCD variable.
5) To ensure that the number of decimal places is correct, the format "DEC.1" must be
used for the PCD variable in the WVAR file in the Web Editor 8 project.