background image

Comparison of LiteTouch and Savant SmartLighting 

The next two figures show the key di

ff

erences between the LiteTouch and Savant SmartLighting systems.

!"#$%&&'()$*+,-./'0,12,"*"$#

!"#$%&&'()*+%,#

LiteTouch Installation and Troubleshooting Manual

31

1. At each keypad backbox, splice the keypad pigtail (shipped with each 

keypad) to the keypad homerun. Always use the pigtail that comes 
with the keypad, as some newer or older models use different pigtails 
and they cannot be mixed.

Use crimp connectors or wirenuts for the connections. The following 
picture identifies the colors for each wire. In a LiteTouch cable, the 
white wire is reserved as a spare.

2. Each keypad is custom labeled and designed for a specific location in 

the home. The keypad address is indicated on the box label. Refer to 
the Keypad Design Schedule to identify the keypad address for each 
keypad.

Each keypad is assigned a unique keypad address. This address is set 
at the factory, but you should verify that it is correct before installing 
the keypad, and change it if necessary.

Two rotary switches are located on each keypad. The location of the 
rotary switches depends on the keypad model, as shown in the follow-
ing two illustrations (the rotary address switches on Metropolitan 
Series keypads are on the front).

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

LiteTouch Control Station Wire

White Spare Wire 16 ga.

Blue 16 ga. (D)
Black 16 ga. (

Ð

)

Red 16 ga. (

+

)

NOTE:

 Voltage readings at this end should typically

read 1 or 2 volts less than at the CCU end.

Use crimp

connectors or

wirenuts.

(Crimp connectors are preferred.)

Keep the control station in its protective plastic bag until all construction work is completed.

!"#$%&&'()$*+,-./'0,12,"*"$#

!"#$%&&'()*+%,#

LiteTouch Installation and Troubleshooting Manual

31

1. At each keypad backbox, splice the keypad pigtail (shipped with each 

keypad) to the keypad homerun. Always use the pigtail that comes 
with the keypad, as some newer or older models use different pigtails 
and they cannot be mixed.

Use crimp connectors or wirenuts for the connections. The following 
picture identifies the colors for each wire. In a LiteTouch cable, the 
white wire is reserved as a spare.

2. Each keypad is custom labeled and designed for a specific location in 

the home. The keypad address is indicated on the box label. Refer to 
the Keypad Design Schedule to identify the keypad address for each 
keypad.

Each keypad is assigned a unique keypad address. This address is set 
at the factory, but you should verify that it is correct before installing 
the keypad, and change it if necessary.

Two rotary switches are located on each keypad. The location of the 
rotary switches depends on the keypad model, as shown in the follow-
ing two illustrations (the rotary address switches on Metropolitan 
Series keypads are on the front).

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

LiteTouch Control Station Wire

White Spare Wire 16 ga.

Blue 16 ga. (D)
Black 16 ga. (

Ð

)

Red 16 ga. (

+

)

NOTE:

 Voltage readings at this end should typically

read 1 or 2 volts less than at the CCU end.

Use crimp

connectors or

wirenuts.

(Crimp connectors are preferred.)

Keep the control station in its protective plastic bag until all construction work is completed.

!"#$%&&'()$*+,-./'0,12,"*"$#

!"#$%&&'()*+%,#

LiteTouch Installation and Troubleshooting Manual

31

1. At each keypad backbox, splice the keypad pigtail (shipped with each 

keypad) to the keypad homerun. Always use the pigtail that comes 
with the keypad, as some newer or older models use different pigtails 
and they cannot be mixed.

Use crimp connectors or wirenuts for the connections. The following 
picture identifies the colors for each wire. In a LiteTouch cable, the 
white wire is reserved as a spare.

2. Each keypad is custom labeled and designed for a specific location in 

the home. The keypad address is indicated on the box label. Refer to 
the Keypad Design Schedule to identify the keypad address for each 
keypad.

Each keypad is assigned a unique keypad address. This address is set 
at the factory, but you should verify that it is correct before installing 
the keypad, and change it if necessary.

Two rotary switches are located on each keypad. The location of the 
rotary switches depends on the keypad model, as shown in the follow-
ing two illustrations (the rotary address switches on Metropolitan 
Series keypads are on the front).

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

LiteTouch Control Station Wire

White Spare Wire 16 ga.

Blue 16 ga. (D)
Black 16 ga. (

Ð

)

Red 16 ga. (

+

)

NOTE:

 Voltage readings at this end should typically

read 1 or 2 volts less than at the CCU end.

Use crimp

connectors or

wirenuts.

(Crimp connectors are preferred.)

Keep the control station in its protective plastic bag until all construction work is completed.

!"#$%&&'()$*+,-./'0,12,"*"$#

!"#$%&&'()*+%,#

LiteTouch Installation and Troubleshooting Manual

31

1. At each keypad backbox, splice the keypad pigtail (shipped with each 

keypad) to the keypad homerun. Always use the pigtail that comes 
with the keypad, as some newer or older models use different pigtails 
and they cannot be mixed.

Use crimp connectors or wirenuts for the connections. The following 
picture identifies the colors for each wire. In a LiteTouch cable, the 
white wire is reserved as a spare.

2. Each keypad is custom labeled and designed for a specific location in 

the home. The keypad address is indicated on the box label. Refer to 
the Keypad Design Schedule to identify the keypad address for each 
keypad.

Each keypad is assigned a unique keypad address. This address is set 
at the factory, but you should verify that it is correct before installing 
the keypad, and change it if necessary.

Two rotary switches are located on each keypad. The location of the 
rotary switches depends on the keypad model, as shown in the follow-
ing two illustrations (the rotary address switches on Metropolitan 
Series keypads are on the front).

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

LiteTouch Control Station Wire

White Spare Wire 16 ga.

Blue 16 ga. (D)
Black 16 ga. (

Ð

)

Red 16 ga. (

+

)

NOTE:

 Voltage readings at this end should typically

read 1 or 2 volts less than at the CCU end.

Use crimp

connectors or

wirenuts.

(Crimp connectors are preferred.)

Keep the control station in its protective plastic bag until all construction work is completed.

!"#$%&&'$()'**+

!"#$%&&'()$*+,-./'0,12,"*"$#

60

LiteTouch Installation and Troubleshooting Manual

Connect data cables to modules and the transorb board

String enclosures together (large installations or multiple enclosures)

Connect the data homeruns to the CCU module ports

Connect the keypad homeruns to the CCU keypad ports

Run an AC power line to the CCU (5000LC only)

The following 5000LC wiring diagram shows the keypad, power, and data 
connections, and the AC power connection to the power supply.

DC Power Lines
from LiteTouch 
Pwer Supplies

To AC Power

Control Station
Homeruns

Data Homeruns From Modules

ILSCO

Ground

Lug

Ground

Neutral

!"#$%&&'$()'**+

!"#$%&&'()$*+,-./'0,12,"*"$#

64

LiteTouch Installation and Troubleshooting Manual

Wire a data line from the transorb board on one enclosure to the transorb 
board on the next enclosure (see previous illustration). Connect the wires 
to the screw terminals at the top of the board, as shown below.

Be sure to connect all five wires, including the shield wire.

*,"")-$'.%$%

/,0)12"#

LiteTouch number 08-2105-01 wire is recommended for data wiring. It 
contains two twisted-pair, 22-gauge wires and an insulated bare shield 
wire. The cable is shielded with mylar.

The cable color used for data homeruns is green.

1. Connect the data homerun cable to the screw terminals at the top of the 

transorb board on the enclosure or the first enclosure of a string. Be 
sure to connect all wires, including the shield wire.

If you are connecting an enclosure string, connect the data homerun to 
the same terminal as the data line connecting the enclosures.

Legacy Transorb Board

Legacy LiteTouch Configuration

120-240V AC

Control Stations/Keypads

!"#$%&&'()$*+,-./'0,12,"*"$#

!"#$%&&'$()'**+

LiteTouch Installation and Troubleshooting Manual

63

string leaves all modules beyond the failure without communication to the 
CCU.

!"#$

 

!"#$%"&#'($)&*#$+(*,&-$)&*#.$&-$/"#$(,/,$0,1'#$23%/$1#$04--#0/#($/4$#,0"$24(5

3'#6$/4$#,0"$/*,-%4*1$14,*(6$,-($/4$/"#$7789$:/$%#*;#%$,%$,$<*43-($*#=#*#-0#$

=4*$04223-&0,/&4-%9

LiteTouch number 08-2105-01 wire is recommended for data wiring. It 
contains two twisted-pair, 22-gauge wires and an insulated bare shield 
wire. The cable is shielded with mylar. The table below shows LiteTouch 
wire colors. The cable color used for data wiring is green.

6800-202

UL

®

LISTED

71TO

IND. CONT. EQ.

®

LR50210

3550 SO. 700 WEST  •  SLC., UTAH 84119  •  (801) 268-8 668  •  FAX (801) 268 -9200  •  TECH HOT LINE 1-800-527- 5527

WARNING

A SHO RTED LOA D WILL  DAMAGE  MODULE..

THIS IS NOT CO VERED  BY WA RRANTY.

TO A VOID  POSSIBLE  DAMAGE TO  MODULE

AC  POWER  MUST  BE  REMOVED  BEFORE

CONNECTING O R  DISCONNECTING LOA DS. 

®

Rated 2 Amps 15 Volts Max.

Neutral

120 VA C
60  HZ

Neutral

120 VA C
60  HZ

WIRE  RANGE 10-16 AW G.   /  TO RQUE 10-12 IN. L BS.   /  60 

c  MIN. CO PPER WI RE ONL Y

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

P

ower

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

LISTED

71TO

IND. CONT. EQ.

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

1  st   DIGIT

2 st  DIGIT

POWER

ADDRESS
SWITCHES

NEUTRAL 1

LINE 1

LOAD 1

LINE 2

LOAD 2

LINE 3

LOAD 3

LINE 4

LOAD 4

LINE 5

LOAD 5

LINE 6

LOAD 6

LINE 7

LOAD 7

LINE 8

LOAD 8

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5
6
7
8
9

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE
LOAD
LED'S

INTERRLOCK
SWITCHES

REMOTE
MANUAL
ON

COMM ON

MANUAL
ON

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.
TO  TEST  FOR  SHORT,  CONNECT  LINE  TO
LOADS  AND A PPLY  POWER  BEFORE

CONNECTING  LOADS  TO  SSC M ODULE.
TO AV OID  POSSIBLE  DAMAGE  TO M ODULE

AC  POWER M UST  BE R EMOVED  BEFORE

CONNECTING  OR  DISCONNECTING  LOADS. 

WIRE RA NGE 12 -22 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY

®

UL

®

UL

®

SERIAL NO.

RELAY RATINGS

VOLTAGE

INC.

FLUOR.

LV.

LOAD TYPE

RATING
8.3A @ 120/250V AC

12A @ 120/250V AC

12A @ 120/250V AC

AC
60 Hz

1/2 HP @ 120VAC

1 HP @ 240VAC

MOTOR

SERIAL  NO.  _________________

C

12345678

R

elay

6800-202

UL

®

LISTED

71TO

IND. CONT. EQ.

®

LR50210

3550 SO. 700 WEST  •  SLC., UTAH 84119  •  (801) 268-8 668  •  FAX (801) 268-9200  •  TECH HOT LINE 1-800 -527-5527

WARNING

A SHO RTED LOA D WILL  DAMAGE  MODULE..

THIS IS NOT CO VERED  BY WA RRANTY.

TO A VOID  POSSIBLE  DAMAGE TO  MODULE

AC  POWER  MUST  BE  REMOVED  BEFORE

CONNECTING O R  DISCONNECTING LOA DS. 

®

Rated 2 Amps 15 Volts Max.

Neutral

120 VA C
60  HZ

Neutral

120 VA C
60  HZ

WIRE  RANGE 10-16 AW G.   /  TO RQUE 10-12 IN. L BS.   /  60 

c  MIN. CO PPER WI RE ONL Y

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

P

ower

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

LISTED

71TO

IND. CONT. EQ.

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

1  st   DIGIT

2 st  DIGIT

POWER

ADDRESS
SWITCHES

NEUTRAL 1

LINE 1

LOAD 1

LINE 2

LOAD 2

LINE 3

LOAD 3

LINE 4

LOAD 4

LINE 5

LOAD 5

LINE 6

LOAD 6

LINE 7

LOAD 7

LINE 8

LOAD 8

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5
6
7
8
9

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE
LOAD
LED'S

INTERRLOCK
SWITCHES

REMOTE
MANUAL
ON

COMM ON

MANUAL
ON

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.
TO  TEST  FOR  SHORT,  CONNECT  LINE  TO
LOADS  AND A PPLY  POWER  BEFORE

CONNECTING  LOADS  TO  SSC M ODULE.
TO AV OID  POSSIBLE  DAMAGE  TO M ODULE

AC  POWER M UST  BE R EMOVED  BEFORE

CONNECTING  OR  DISCONNECTING  LOADS. 

WIRE RA NGE 12 -22 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY

®

UL

®

UL

®

SERIAL NO.

RELAY RATINGS

VOLTAGE

INC.

FLUOR.

LV.

LOAD TYPE

RATING
8.3A @ 120/250V AC

12A @ 120/250V AC

12A @ 120/250V AC

AC
60 Hz

1/2 HP @ 120VAC

1 HP @ 240VAC

MOTOR

SERIAL  NO.  _________________

C

12345678

R

elay

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD
LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE
AND  CAN  DAMAGE M ODULE.
THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 
WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

R

1

1

RECEIVE -

RECEIVE -

2

2

T

T

3

3

TRANSIT -

TRANSIT -

4

4

GND/SHIELD

GND/SHIELD

5

5

R

R

1

1

RECEIVE -

RECEIVE -

2

2

T

T

3

3

TRANSIT -

TRANSIT -

4

4

GND/SHIELD

GND/SHIELD

5

5

DATA IN

DATA IN

DATA OUT

DATA OUT

ACTIVE 

OUTPUT

LEDS

ACTIVE 

OUTPUT

LEDS

MFG. CODE

MFG. CODE

Label P/N 6800-266.01

Label P/N 6800-266.01

LOAD TYPE

LOAD TYPE

GENERAL PURPOSE

GENERAL PURPOSE

ADDRESS 

ADDRESS 

SWITCHES

SWITCHES

1st 

1st 

DIGIT

DIGIT

2nd 

2nd 

DIGIT

DIGIT

1
2
3
4
5
6
7
8
9

1
2
3
4
5
6
7
8
9

COMMON

COMMON

MANUAL
REMOTE
ON

MANUAL
REMOTE
ON

C

C

RELAY RATINGS

RELAY RATINGS

12 A/120 VAC MAX. PER OUTPUT
96 A/120 VAC MAX. PER MODULE

12 A/120 VAC MAX. PER OUTPUT
96 A/120 VAC MAX. PER MODULE

A SHORTENED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE.  
THIS IS NOT COVERED BY WARRANTY

A SHORTENED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE.  
THIS IS NOT COVERED BY WARRANTY

WARNING

WARNING

LINE 1 AND NEUTRAL 1 MUST BE 
CONNECTED TO POWER THE MODULE 

LINE 1 AND NEUTRAL 1 MUST BE 
CONNECTED TO POWER THE MODULE 

3400 SOUTH WEST TEMPLE     SLC, UTAH 84115     (801) 486-8500     FAX 801-486-8569      

3400 SOUTH WEST TEMPLE     SLC, UTAH 84115     (801) 486-8500     FAX 801-486-8569      

TECHNICAL SUPPORT 1-800-527-5527

TECHNICAL SUPPORT 1-800-527-5527

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

MANUAL 
ON

WIRE RANGE 10-16 AWG.

TORQUE 7  IN. LBS.

60 c MIN. COPPER WIRE ONLY.

WIRE RANGE 10-16 AWG.

TORQUE 7  IN. LBS.

60 c MIN. COPPER WIRE ONLY.

USE SLOW BLOW 12 AMP FUSES.

USE SLOW BLOW 12 AMP FUSES.

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

MOTOR

MOTOR

1 HP @ 240 VAC PER CHANNEL
1/2 HP @ 120 VAC PER CHANNEL

1 HP @ 240 VAC PER CHANNEL
1/2 HP @ 120 VAC PER CHANNEL

POWER

POWER

ADDRESS

OFF/ON

1-2
3-4
5-6
7-8

1-2
3-4
5-6
7-8

OFF/ON

INTERLOCK
SWITCHES

NEUTRAL

NEUTRAL

LOAD NO.

LOAD NO.

1

2

3

4

5

6

7

8

R

elay

R

R

1

1

RECEIVE -

RECEIVE -

2

2

T

T

3

3

TRANSIT -

TRANSIT -

4

4

GND/SHIELD

GND/SHIELD

5

5

R

R

1

1

RECEIVE -

RECEIVE -

2

2

T

T

3

3

TRANSIT -

TRANSIT -

4

4

GND/SHIELD

GND/SHIELD

5

5

DATA IN

DATA IN

DATA OUT

DATA OUT

ACTIVE 

OUTPUT

LEDS

ACTIVE 

OUTPUT

LEDS

MFG. CODE

MFG. CODE

Label P/N 6800-266.01

Label P/N 6800-266.01

LOAD TYPE

LOAD TYPE

GENERAL PURPOSE

GENERAL PURPOSE

ADDRESS 

ADDRESS 

SWITCHES

SWITCHES

1st 

1st 

DIGIT

DIGIT

2nd 

2nd 

DIGIT

DIGIT

1
2
3
4
5
6
7
8
9

1
2
3
4
5
6
7
8
9

COMMON

COMMON

MANUAL
REMOTE
ON

MANUAL
REMOTE
ON

C

C

RELAY RATINGS

RELAY RATINGS

12 A/120 VAC MAX. PER OUTPUT
96 A/120 VAC MAX. PER MODULE

12 A/120 VAC MAX. PER OUTPUT
96 A/120 VAC MAX. PER MODULE

A SHORTENED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE.  
THIS IS NOT COVERED BY WARRANTY

A SHORTENED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE.  
THIS IS NOT COVERED BY WARRANTY

WARNING

WARNING

LINE 1 AND NEUTRAL 1 MUST BE 
CONNECTED TO POWER THE MODULE 

LINE 1 AND NEUTRAL 1 MUST BE 
CONNECTED TO POWER THE MODULE 

3400 SOUTH WEST TEMPLE     SLC, UTAH 84115     (801) 486-8500     FAX 801-486-8569      

3400 SOUTH WEST TEMPLE     SLC, UTAH 84115     (801) 486-8500     FAX 801-486-8569      

TECHNICAL SUPPORT 1-800-527-5527

TECHNICAL SUPPORT 1-800-527-5527

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

MANUAL 
ON

WIRE RANGE 10-16 AWG.

TORQUE 7  IN. LBS.

60 c MIN. COPPER WIRE ONLY.

WIRE RANGE 10-16 AWG.

TORQUE 7  IN. LBS.

60 c MIN. COPPER WIRE ONLY.

USE SLOW BLOW 12 AMP FUSES.

USE SLOW BLOW 12 AMP FUSES.

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

NO. 1
NO. 2
NO. 3
NO. 4
NO. 5
NO. 6
NO. 7
NO. 8

MOTOR

MOTOR

1 HP @ 240 VAC PER CHANNEL
1/2 HP @ 120 VAC PER CHANNEL

1 HP @ 240 VAC PER CHANNEL
1/2 HP @ 120 VAC PER CHANNEL

POWER

POWER

ADDRESS

OFF/ON

1-2
3-4
5-6
7-8

1-2
3-4
5-6
7-8

OFF/ON

INTERLOCK
SWITCHES

NEUTRAL

NEUTRAL

LOAD NO.

LOAD NO.

1

2

3

4

5

6

7

8

R

elay

6800-218

3550 SO. 700 WEST  •  SLC., UTAH  84119  •  (801) 268-8 668  •  FAX (801) 268-9200  •  TECH HOT LINE 1-800-527- 5527

WARNING

A SHO RTED LOA D WILL  DAMAGE  MODULE.

THIS IS NOT CO VERED  BY WA RRANTY.

TO A VOID  POSSIBLE  DAMAGE TO  MODULE

AC  POWER  MUST  BE  REMOVED  BEFORE

CONNECTING O R  DISCONNECTING LOA DS. 

RATINGS

PRIMAR Y: 2 AM PS, 12 0 VA C MA X.
SECONDARY: 15 - 20 V DC  UNREGULATED

Neutral

120 VA C

60  HZ

Neutral

120 VA C

60  HZ

WIRE  RANGE 10-16 AW G.   /  TO RQUE 10-12 IN. L BS.   /  60  MIN. CO PPER WI RE ONL Y

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

®

C

C

DATE:

P

ower

6800-218

3550 SO. 700 WEST  •  SLC., UTAH  84119  •  (801) 268-8 668  •  FAX (801) 268-9200  •  TECH HOT LINE 1-800-527- 5527

WARNING

A SHO RTED LOA D WILL  DAMAGE  MODULE.

THIS IS NOT CO VERED  BY WA RRANTY.

TO A VOID  POSSIBLE  DAMAGE TO  MODULE

AC  POWER  MUST  BE  REMOVED  BEFORE

CONNECTING O R  DISCONNECTING LOA DS. 

RATINGS

PRIMAR Y: 2 AM PS, 12 0 VA C MA X.
SECONDARY: 15 - 20 V DC  UNREGULATED

Neutral

120 VA C

60  HZ

Neutral

120 VA C

60  HZ

WIRE  RANGE 10-16 AW G.   /  TO RQUE 10-12 IN. L BS.   /  60  MIN. CO PPER WI RE ONL Y

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC  Pos.

DC  Com.

FUSE A GC 5 Amp.

NOT USE D

®

C

C

DATE:

P

ower

Transorb

Board

Transorb

Board

Transorb

Board

Transorb

Board

From power supply to CCU

and control station connector(s)

TO FIRST ENCLOSURE

TRANSORB BOARD

From power supply to CCU

and control station connector(s)

TO CCU

,-$)./01('2-3)'*/&/3#

Red
Black
White (spare)
Green
Bare (shielded)

DC Power Lines from LiteTouch Power Supplies

to module enclosure 

Legacy LiteTouch Configuration

An example Savant SmartLighting system is shown in the next figure with the SSL-P018 and the 
SKL-4000 components.

NOTE

:  If  PoE  is  not  present,  installer  may  purchase  a  power  supply:  12V  DC,  120-240V  AC, 

50/60 Hz (PWR-12125).

Savant SmartLighting Configuration

SSL-P018

Network

Up to 40 keypads per  SKL-4000

SKL-4000

110-240V AC input 

Power Supply

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

Control Station Backbox

Control Station Backbox

Control Station Backbox

CONNECTOR

3 PIN

CONNECTOR

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

Control Station Backbox

Control Station Backbox

Control Station Backbox

CONNECTOR

3 PIN

CONNECTOR

Up to 8 SKL-4000s or 256 keypad addresses per SSL-P018

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

Control Station Backbox

Control Station Backbox

Control Station Backbox

CONNECTOR

3 PIN

CONNECTOR

Control Station Backbox

Control Station Backbox

Control Station Backbox

3 PIN

CONNECTOR

3 PIN

CONNECTOR

Control Station Backbox

Control Station Backbox

Control Station Backbox

CONNECTOR

3 PIN

CONNECTOR

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

R

WIRE RANGE 10-16 AWG.

TORQUE 7 IN. LBS. 

60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.

TORQUE 7 IN. LBS. 

60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.

TORQUE 7 IN. LBS. 

60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.

TORQUE 7 IN. LBS. 

60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

Transorb

Board

Transorb Board

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 34

5

67

89

AB

C

D

E F

01 2 34

5

67

89

AB

C

D

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

®

®

LISTED

71TO

IND. CONT. EQ.

1  st  
DIGIT
2  nd 
DIGIT

ADDRESS
SWITCHES

ADDRESS

RATED 2 0 AM PS  TOTAL, 12 0 V OLTS  TUNGSTEN

NOT  TO  EXCEED 1 6   AM PS  ON A NY  SINGLE  OUTPUT

CAUTION R ISK  OF  ELECTRICAL  SHOCK.  HEAT  SINK

IS  LIVE.  DISCONNECT  FROM  POWER  BEFORE  SERVICING.

®

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  IN

1
2
3
4
5

RECEIVE  +
RECEIVE   –
TRANSMIT  +
TRANSMIT   –
GND/SHIELD

DATA  OUT

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

NO. 1
NO. 2
NO.  3
NO.  4
NO. 5
NO.  6
NO.  7
NO.  8

ACTIVE  LOAD

LEDS

3550  SO.  700  WEST  •   SLC.,  UTAH  84119  •   (801) 2 68-8668  •   FAX  (801) 2 68-9200  •   TECH  HOT  LINE 1 -800-527-5527

WARNING

A  SHORTED  LOAD  WILL  BLOW  FUSE

AND  CAN  DAMAGE M ODULE.

THIS  IS  NOT  COVERED  BY  WARRANTY.

WIRE RA NGE 1 0-16 A WG.

TORQUE 1 0-12  IN.  LBS.

60  c M IN.  COPPER  WIRE  ONLY
USE  FAST A CTING 2 0 AM P  FUSES.

1
2
3
4
5
6
7
8

MANUAL
OFF    ON

SERIAL  NO.  ____________________________________

POWER

1
2
3
4
5
6
7
8

REMOTE
MANUAL
ON

COMMON

C

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

R

WIRE RANGE 10-16 AWG.
TORQUE 7 IN. LBS. 
60  c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINK
IS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE AND

CAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY. 

WHEN DRIVING TRANSFORMER COUPLED

LOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/A

RATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER 

MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE

Label P/N 6800-258.01

ADDRESS

MANUAL
ON

ACTIVE
OUTPUT
LEDS

MANUAL
REMOTE
ON

INPUT120 VAC 

60 Hz.

LOAD TYPE

LOAD TYPE

TUNGSTEN

TUNGSTEN

RELAY RATING

RELAY RATING

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT
20 A/120 VAC MAX. PER OUTPUT
40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

D

imm er

Transorb

Board

Transorb Board

Up to 16-Module Enclosures or 16 Transorb Boards per 

port on SSL-P018 (64 module addresses*)

*Some modules use two addresses

If all 4 module ports are used, up to 256 module addresses are available.

Standard CAT 5/6 cable

RJ-45 Connector

Station Bus Wire 

3-pin Connector (16-gauge)

Module Jumper Wire 

5-pin Connector

(22-gauge)

CAT 5/6 cable with PoE

To More Module Enclosures,

if necessary

Savant SmartLighting Configuration

140915   009-0885-01  Savant SmartLighting Control Conversion Application 

5     of    22

Содержание SmartLighting

Страница 1: ...Number 009 0885 01 1 of 22 Copyright 2014 Savant Systems LLC SAVANT and RacePoint Blueprint are trademarks of Savant Systems LLC All brand names product names and trademarks are the property of their...

Страница 2: ...les 8 Removing and Replacing a Transorb Board 9 Installing a SmartLighting Controller 10 Connecting a Savant SmartLighting Controller to an SKL 1000 11 Installing a Savant Keypad Link 13 Connecting a...

Страница 3: ...tant Savant SmartLighting products have been redesigned to be more efficient and are automatically integrated Some of the older legacy out of warranty products may no longer be compatible with this ne...

Страница 4: ...rb boards 5 Install SmartLighting controller 6 Install Savant Keypad Links 7 Confirm the rewiring as follows New transorb board connected to SmartLighting controller via Cat 5 5e 6 cable New transorb...

Страница 5: ...RESS MANUAL ON ACTIVE OUTPUT LEDS MANUAL REMOTE ON INPUT120 VAC 60 Hz LOAD TYPE LOAD TYPE TUNGSTEN TUNGSTEN RELAY RATING RELAY RATING 15 A 120 VAC MAX PER OUTPUT 20 A 120 VAC MAX PER OUTPUT 40 A 120 V...

Страница 6: ...andard and compact CCUs do not use prg files The standard and compact CCU definition files def and cdf respectively must be converted to prg files Note that the CCU communicates with LiteWare using ei...

Страница 7: ...roller Type previously selected 7 Click From Controller 8 Browse to the location where you would like the extracted prg file stored and click Save The status pane in the Control Panel will show the pr...

Страница 8: ...d into LiteWare as an LW4 file 4 Click the Job Parameters tab 5 Under Controller Selection for Type select either SSL P018 or SSL P002 from the drop down list 6 From the main menu select File Save As...

Страница 9: ...than eight enclosures or when you have mul tiple enclosure locations you can string enclosures together to reduce the number of data homeruns to the CCU While this helps to simplify the wiring you sh...

Страница 10: ...module which is connected to the tran sorb board via the 5 pin connector 0 1 2 3 42 In large installations more than eight enclosures or when you have mul tiple enclosure locations you can string encl...

Страница 11: ...n the SmartLighting system you must configure the SSL P002 or SSL P018 to communicate using the same serial port standard By default the SKL 1000 uses RS 232 The SSL P002 or SSL P018 use RS 422 To set...

Страница 12: ...ect the Unique ID UID that matches the UID on the sticker of the SSL P018 or the SSL P002 3 Open a browser and enter the IP address of the SSL P018 or the SSL P002 4 Select Serial Ports on the sidebar...

Страница 13: ...not compliant with the new device rewiring or other reconfiguration will be necessary To connect the SKL 4000 to a SmartLighting controller SSL P018 or SSL P002 do the following 1 Using Cat 5 5e 6 ca...

Страница 14: ...ion bus ports circled in the next figure 5 To use the bus ports for connecting to keypads splice the 16 AWG or 18 AWG wiring and attach the wires to the three pin connector based on the following posi...

Страница 15: ...n boxes plaster or tile rings are not acceptable In new construction installations for example a single gang backbox model P 241 supplied by Allied Moulded Products would accommodate a Savant keypad A...

Страница 16: ...martLighting controller The SmartLighting controller communicates with LiteWare using an Ethernet connection To export the LiteWare prg file to an SSL P018 or SSL P002 do the following 1 Open LiteWare...

Страница 17: ...6 Confirm the TCP IP Settings IP Address and Port 7 Click To Controller 8 Browse to the prg file that you previously extracted from the CCU and click Open The status pane in the Control Panel will sho...

Страница 18: ...eypads Keypads S H E Capri Coastal Hybrids Metropolitan G2 Circa Echo 1000 2600 Series Metropolitan Circa Echo As of January 1 2013 we have three keypad models of various configurations Enclosures Enc...

Страница 19: ...8 2150 03 0 10 VDC 277V MIXED 007 PS and LV Relay MIXED 008 PS and Mom D I Module MIXED 009 PS and Maint D I Module MIXED 004 LV Relay and Mom D I Module MIXED 005 LV Relay and Maint D I Module MIXED...

Страница 20: ...porated AirPlay Apple AirPort Express AirPort Extreme Apple TV Apple Remote Desktop FireWire iMac iTunes iPad iPad mini iPhone iPod touch MacBook Mac and OS X are trademarks or trade names of Apple In...

Страница 21: ...document Caution describes a situation that may cause damage to the equipment Warning In this document Warning describes a situation that may present a physical danger to the installer or end user Ele...

Страница 22: ...he provided plug does not fit into your outlet consult an electrician for replacement of the obsolete outlet 10 Protect the power cord from being walked on or pinched particularly at plugs convenience...

Отзывы: